9 - 71
9 Communications Functions
High-function General-purpose Inverter RX2 Series User’s Manual
9-
5 Mod
bu
s Com
m
u
n
icat
ion
Regi
ster Nu
m
b
er
List
9
9-5-
5 Group b
Register
List
5AAAh
33A9h
Electronic thermal level set-
ting, 2nd-motor
bC210
R/W
Same as bb110
0.1(A)
5AABh
5AAAh
Electronic thermal character-
istic selection, 2nd-motor
bC211
R/W
Same as bb111
-
5AACh
5AABh
Electronic thermal Subtraction
function enable, 2nd-motor
bC212
R/W
Same as bC112
-
5AADh
5AACh
Electronic thermal Subtraction
time, 2nd-motor
bC213
R/W
Same as bC113
1(s)
5AB4h
5AB3h
Free electronic thermal fre-
quency-1, 2nd-motor
bC220
R/W
0.00 to [bC222] (Hz)
0.01(Hz)
5AB5h
5AB4h
Free electronic thermal cur-
rent-1, 2nd-motor
bC221
R/W
Same as bC121
0.1(A)
5AB6h
5AB5h
Free electronic thermal fre-
quency-2, 2nd-motor
bC222
R/W
[bC220] to [bC224] (Hz)
0.01(Hz)
5AB7h
5AB6h
Free electronic thermal cur-
rent-2, 2nd-motor
bC223
R/W
Same as bC123
0.1(A)
5AB8h
5AB7h
Free electronic thermal fre-
quency-3, 2nd-motor
bC224
R/W
[bC222] to 590.00 (Hz)
0.01(Hz)
5AB9h
5AB8h
Free electronic thermal cur-
rent-3, 2nd-motor
bC225
R/W
Same as bC125
0.1(A)
*1. On the parameter about the current and the voltage, the figures and the units to be handled vary in the setting path.
1) Operator or CX-Drive: 0.1 A or 0.1 V (When CX-Drive is operated, set [CF-11] Resister data selection to 00 (A, V).
When the data of [CF-11] Resister data selection is not set to 00 (A, V), it is not set or displayed correctly.)
2) Modbus: The current and the voltage vary, depending on the setting of Resister data selection [CF-11].
When [CF-11] Resister data selection is set to 00 (A, V), 0.1 A, 0.1 V
When [CF-11] Resister data selection is set to 01 (%), 0.01% (Rated ratio)
3) Drive programming: 0.01% (Rated ratio)
*2. Minimum resistance values vary in inverter model.
*3. 3G3RX2-B4750 to 3G3RX2-B413K shall be as follows.
[Ub-03]=02: 0.5 to 10.0(kHz)
[Ub-03]=00 or 01: 0.5 to 8.0(kHz)
*4. The feedback input to input terminals A and B and the feedback input to option cassette RX2-PG are necessary.
Register
No.
Modbus
register
spec. No.
Function name
Parame-
ter No.
R/W
Monitor or setting data
Resolution
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......