9 Communications Functions
9 - 102
High-function General-purpose Inverter RX2 Series User’s Manual
The sequence diagram below shows co-inverter communication among four inverters with station num-
bers from 1 to 4, where Stations No. 1 to 3 are set as the master inverter.
• Be sure to set the Communication Error Timeout Time (CF-06) to other than 0.00 (1 second or longer
is recommended) on the management inverter. When this parameter is set to 0.00, the inverter’s
communications function will stop if no data is received from the master. If it stops working, cycle the
power supply of the management inverter.
• The communications error timeout timer starts when the inverter starts waiting for data reception and
times out when it cannot complete data reception within the set time. If a timeout occurs, the inverter
performs the operation set in the Operation Selection on Communication Error (CF-05). (t3 in above
diagram)
• When the management inverter is the master, the master switching command will be sent with a wait
time of “silent interval
Communication Wait Time (CF-07) after the master sends data. (t1 in above
diagram)
• When an inverter other than the management inverter is the master, the master switching command
will be sent with a wait time of “silent interval
Communication Wait Time (CF-07) after receipt of
data sent from the master inverter. (t2 in above diagram)
• When the Co-inverter Communication Start Selection (C100) is set to 01 (Constant communication),
the management inverter starts sending data as soon as the power supply is turned on. Therefore, if
the power-on timing of any other inverter is delayed, the communications cannot be established nor-
mally, which results in a communications timeout error on the management inverter. When you set
this to 01 (Constant communication), check that the startup of the other inverters is completed and
power on the management inverter finally.
• Do not set (EEPROM Write) or (EEPROM Write Mode Selection) in the recipient registers. Doing so
causes the co-inverter communication session to stop in the EEPROM write process.
• After changing any of the CF-08, CF-20 to CF-22 data, be sure to cycle the power supply to apply
the changes.
Example of Inter-inverter Communication Sequence
M
S
S
S
M
S
S
S
M
S
S
S
M
S
S
S
02 xxxx xxxx
02 xxxx xxxx
03 xxxx xxxx
03 xxxx xxxx
t3
t2
t3
t3
t1
M
S
t3
Up to 5 recipients
can be specified.
Station No. register data
Data sent from master
Data received by slave(s)
Master switching command
Inverter Station No. 1
Inverter Station No. 2
Inverter Station No. 3
Inverter Station No. 4
Management
Send
Receive
Send
Receive
Send
Receive
Send
Receive
All slaves receive data from the
master but discard it if not destined
to them.
t1: Silent Interval
Communication Wait Time (CF-07)
t2: Silent Interval
Communication Wait Time (CF-07)
t3: Communication Error Timeout Time (CF-06)
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......