Appendices C Table of Parameters
C - 56
High-function General-purpose Inverter RX2 Series User’s Manual
Code
Codes that
can be
changed
during
operation
Name
Data range
Initial
value
Note
CF-01
-
RS485 communication baud rate
selection
03 (2400bps)/04 (4800bps)/05 (9600bps)/06 (19.2kbps)/
07 (38.4kbps)/08 (57.6kbps)/09 (76.8kbps)/
10 (115.2kbps)
05
CF-02
○
RS485 communication Node allo-
cation
1 to 247
1
CF-03
○
RS485 communication parity
selection
00 (Without parity)/
01 (Even number parity)/02 (Odd number parity)
00
CF-04
○
RS485 communication stop-bit
selection
01 (1bit)/02 (2bit)
01
CF-05
○
RS485 communication error
selection
00 (Error)/01 (Trip after deceleration stop)/02 (Ignore)/
03 (Free run)/04 (Deceleration stop)
02
CF-06
○
RS485 communication timeout
setting
0.00 to 100.00 (s)
0.00
CF-07
○
RS485 communication wait time
setting
0 to 1000 (ms)
2
CF-08
○
RS485 communication mode
selection
01 (Modbus-RTU)/02 (EzCOM)/
03 (EzCOM management)
01
CF-11
-
Resister data selection
00 (A,V)/01 (%)
00
CF-20
-
EzCOM start node No.
01 to 08
1
CF-21
-
EzCOM End node No.
01 to 08
1
CF-22
-
EzCOM start method selection
00 (ECOM) terminal)/01 (Modbus spec)
00
CF-23
○
EzCOM data size
01 to 05
5
CF-24
○
EzCOM destination address 1
1 to 247
1
CF-25
○
EzCOM destination register 1
0000 to FFFF
0000
CF-26
○
EzCOM source register 1
0000 to FFFF
0000
CF-27
○
EzCOM destination address 2
1 to 247
2
CF-28
○
EzCOM destination register 2
0000 to FFFF
0000
CF-29
○
EzCOM source register 2
0000 to FFFF
0000
CF-30
○
EzCOM destination address 3
1 to 247
3
CF-31
○
EzCOM destination register 3
0000 to FFFF
0000
CF-32
○
EzCOM source register 3
0000 to FFFF
0000
CF-33
○
EzCOM destination address 4
1 to 247
4
CF-34
○
EzCOM destination register 4
0000 to FFFF
0000
CF-35
○
EzCOM source register 4
0000 to FFFF
0000
CF-36
○
EzCOM destination address 5
1 to 247
5
CF-37
○
EzCOM destination register 5
0000 to FFFF
0000
CF-38
○
EzCOM source register 5
0000 to FFFF
0000
CF-50
○
USB communication Node alloca-
tion
1 to 247
1
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......