9 - 79
9 Communications Functions
High-function General-purpose Inverter RX2 Series User’s Manual
9-
5 Mod
bu
s Com
m
u
n
icat
ion
Regi
ster Nu
m
b
er
List
9
9-5-
6 Group C
Register
List
386Eh
386Dh
Window comparator for [Ai3]
higher level
CE-46
R/W
-100 to 100
1(%)
386Fh
386Eh
Window comparator for [Ai3]
lower level
CE-47
R/W
-100 to 100
1(%)
3870h
386Fh
Window comparator for [Ai3]
hysteresis width
CE-48
R/W
0 to 10
1(%)
3872h
3871h
Operation level at [Ai1] dis-
connection
CE-50
R/W
0 to 100
1(%)
3873h
3872h
Operation level selection at
[Ai1] disconnection
CE-51
R/W
00: Disabled
01: Enabled: out of range
02: Enabled: within the range
-
3874h
3873h
Operation level at [Ai2] dis-
connection
CE-52
R/W
0 to 100
1(%)
3875h
3874h
Operation level selection at
[Ai2] disconnection
CE-53
R/W
00: Disabled
01: Enabled: out of range
02: Enabled: within the range
-
3876h
3875h
Operation level at [Ai3] dis-
connection
CE-54
R/W
-100 to 100
1(%)
3877h
3876h
Operation level selection at
[Ai3] disconnection
CE-55
R/W
00: Disabled
01: Enabled: out of range
02: Enabled: within the range
-
38A5h
38A4h
RS485 communication baud
rate selection
CF-01
R/W
03:2400bps
04:4800bps
05:9600bps
06:19.2kbps
07:38.4kbps
08:57.6kbps
09:76.8kbps
10:115.2kbps
-
38A6h
38A5h
RS485 communication Node
allocation
CF-02
R/W
1 to 247
1
38A7h
38A6h
RS485 communication parity
selection
CF-03
R/W
00: Without parity
01: Even number parity
02: Odd number parity
-
38A8h
38A7h
RS485 communication
stop-bit selection
CF-04
R/W
01: 1bit
02: 2bit
-
38A9h
38A8h
RS485 communication error
selection
CF-05
R/W
00: Error
01: Trip after deceleration stop
02: Ignore
03: Free run
04: (Deceleration stop)
-
38Aah
38A9h
RS485 communication time-
out setting
CF-06
R/W
0 to 10000
(0:Disable Communication Time-
out)
0.01(s)
38Abh
38AAh
RS485 communication wait
time setting
CF-07
R/W
0 to 1000
1(ms)
38Ach
38ABh
RS485 communication mode
selection
CF-08
R/W
01: Modbus-RTU
02: EzCOM
03: EzCOM management
-
38AFh
38AEh
Resister data selection
CF-11
R/W
00: A,V
01: %
-
38B8h
38B7h
EzCOM Start node No.
CF-20
R/W
01 to 08
1
38B9h
38B8h
EzCOM End node No.
CF-21
R/W
01 to 08
1
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W
Monitor or setting data
Resolution
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......