2 Design
2 - 2
High-function General-purpose Inverter RX2 Series User’s Manual
Turn off the power supply and implement wiring correctly.
Not doing so may result in a serious injury due to an electric shock.
Wiring work must be carried out only by qualified personnel.
Not doing so may result in a serious injury due to an electric shock.
Do not change wiring and slide switches (SW1 to SW6), put on or take off Operator and optional
devices, replace cooling fans while the input power is being supplied. Doing so may result in a seri-
ous injury due to an electric shock.
Be sure to ground the unit.
Not doing so may result in a serious injury due to an electric shock or fire.
(200-V class: type-D grounding, 400-V class: type-C grounding)
Do not connect resistors to the terminals (PD/+1, P/+, N/-) directly.
Doing so might result in a small-scale fire, heat generation, or damage to the unit.
Install a stop motion device to ensure safety.
Not doing so may result in a minor injury.
(A holding brake is not a stop motion device designed to ensure safety.)
Be sure to use a specified type of braking resistor and regenerative braking unit. In case of using a
braking resistor, install a thermal relay that monitors the temperature of the resistor.
Not doing so may result in a moderate burn due to the heat generated in the braking resistor/regen-
erative braking unit.
Configure a sequence that enables the inverter power to turn off when unusual overheating is
detected in the braking resistor and regenerative braking unit.
The inverter has high voltage parts inside which, if short-circuited, might cause damage to itself or
other property. Place covers on the openings or take other precautions to make sure that no metal
objects such as cutting bits or lead wire scraps go inside when installing and wiring.
Setting wrong parameter at startup, adjustment, maintenance and exchange may result in severe
damage. Operate the device after sufficient checking.
WARNING
Caution
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......