9 Communications Functions
9 - 58
High-function General-purpose Inverter RX2 Series User’s Manual
3201h
3200h
PID2 enable
AJ-01
R/W
00: Disabled
01: Enabled Without reverse out-
put
02: Enabled With reverse output
-
3202h
3201h
PID2 deviation inverse
AJ-02
R/W
00: Disabled
01: Enabled
-
3203h
3202h
PID2 unit selection
AJ-03
R/W
C-70 at the end of Appendices C
-
3204h
3203h
PID2 scale adjustment (at
0%)
AJ-04
R/W
-10000 to 10000
1
3205h
3204h
PID2 scale adjustment (at
100%)
AJ-05
R/W
-10000 to 10000
1
3206h
3205h
PID2 scale adjustment (point
position)
AJ-06
R/W
00:0000.
01:0000.0
02:000.00
03:00.000
04:0.0000
-
3207h
3206h
Input source selection of
Set-point for PID2
AJ-07
R/W
00: Disabled
01: Ai1 terminal input
02: Ai2 terminal input
03: Ai3 terminal input
04: (Reserved)
05: (Reserved)
06: (Reserved)
07: Parameter setting
08: RS 485
09: Option 1
10: Option 2
11: Option 3
12: Pulse string input: Inverter
13: Pulse string input: Option
15: PID calculation
-
320Ah
3209h
Set-point setting for PID2
AJ-10
(HIGH)
R/W
-100.00 to 100.00
*1
Unit differs
depending
on setting
[AJ-03]
[AJ-06].
320Bh
320Ah
AJ-11
(LOW)
R/W
320Ch
320Bh
Input source selection of Pro-
cess data for PID2
AJ-12
R/W
00: Disabled
01: Ai1 terminal input
02: Ai2 terminal input
03: Ai3 terminal input
04: (Reserved)
05: (Reserved)
06: (Reserved)
07: Parameter setting
08: RS 485
09: Option 1
10: Option 2
11: Option 3
12: Pulse string input: Inverter
13: Pulse string input: Option
-
320Dh
320Ch
PID2 proportional gain
AJ-13
R/W
0 to 1000
0.1
320Eh
320Dh
PID2 integral time constant
AJ-14
R/W
0 to 36000
0.1(s)
320Fh
320Eh
PID2 derivative gain
AJ-15
R/W
0 to 10000
0.01(s)
3210h
320Fh
PID2 output range
AJ-16
R/W
0 to 10000
0.01(%)
Register
No.
Modbus
register
spec. No.
Function name
Parameter
No.
R/W
Monitor or setting data
Resolution
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......