Appendices C Table of Parameters
C - 38
High-function General-purpose Inverter RX2 Series User’s Manual
bb-24
-
Selection of restart mode
@Instantaneous power failure/
under-voltage trip
00 (0Hz)/01 (Frequency matching)/
02 (Frequency entrainment)/
03 (Detection speed)/
04 (Trip after frequency matching deceleration
stop)
01
bb-25
-
Allowable under-voltage power
failure time
0.3 to 25.0 (s)
1.0
bb-26
-
Retry wait time before motor
restart
0.3 to 100.0 (s)
0.3
bb-27
-
Instantaneous power fail-
ure/under-voltage trip alarm
enable
00 (Disabled)/01 (Enabled at stop)/
02 (Disabled at stop and deceleration stop)
00
bb-28
-
Selection of restart mode
@over-current
00 (0Hz)/01 (Frequency matching)/
02 (Frequency entrainment)/
03 (Detection speed)/
04 (Trip after frequency matching deceleration
stop)
01
bb-29
-
Wait time of restart @over-cur-
rent
0.3 to 100.0 (s)
0.3
bb-30
-
Selection of restart mode
@over-voltage
00 (0Hz)/01 (Frequency matching)/
02 (Frequency entrainment)/
03 (Detection speed)/
04 (Trip after frequency matching deceleration
stop)
01
bb-31
-
Wait time of restart @over-volt-
age
0.3 to 100.0 (s)
0.3
bb-40
○
Restart mode after FRS release
00 (0Hz)/01 (Frequency matching)/
02 (Frequency entrainment)/
03 (Detection speed)
*2
00
bb-41
○
Restart mode after RS release
00 (0Hz)/01 (Frequency matching)/
02 (Frequency entrainment)/
03 (Detection speed)
*2
00
bb-42
○
Restart frequency threshold
0.00 to 590.00 (Hz)
0.00
bb-43
○
Restart level of Active frequency
matching
(0.0 to 2.0)
× Inverter rated current (A)
*3
1.0
× Inverter
rated current
bb-44
○
Restart constant(speed) of
Active frequency matching
0.10 to 30.00 (s)
0.50
bb-45
○
Restart constant(Voltage) of
Active frequency matching
0.10 to 30.00 (s)
0.50
bb-46
○
OC-supress level of Active fre-
quency matching
(0.2 to 2.0)
× Inverter rated current (A)
*3
1.0
× Inverter
rated current
bb-47
○
Restart speed selection of
Active frequency matching
00 (Cutoff frequency)/
01 (Maximum frequency)/02 (Setting frequency)
00
bb160
-
Over current detection level,
1st-motor
(0.2 to 2.2)
x Inverter ND rated current (A)
*3
2.2
× Inverter ND
rated current
bb-61
○
Power supply over voltage
selection
00 (Warning)/01 (Error)
00
bb-62
○
Power supply over voltage level
setting
(200 V class) 300.0 to 410.0 (V)
(400 V class) 600.0 to 820.0 (V)
(200 V class) 390.0
(400 V class) 780.0
bb-64
-
Ground fault selection
00 (Disabled)/01 (Enabled)
01
bb-65
○
Input phase loss enable
00 (Disabled)/01 (Enabled)
00
bb-66
○
Output phase loss enable
00 (Disabled)/01 (Enabled)
00
bb-67
○
Output phase loss detection
sensitivity
1 to 100 (%)
10
bb-70
○
Thermistor error level
0 to 10000 (Ω)
3000
bb-80
○
Over-speed detection level
0.0 to 150.0 (%)
135.0
bb-81
○
Over-speed detection time
0.0 to 5.0 (s)
0.5
Code
Codes that
can be
changed
during
operation
Name
Data range
Initial value
Note
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......