6 Basic Parameter Settings
6 - 44
High-function General-purpose Inverter RX2 Series User’s Manual
6-5
Limit Frequency and Operation Com-
mands
A limiter of the upper and lower limits of the frequency command can be set. The upper limiter can be
set from analog input by setting [bA101].
This function limits a frequency command even if a frequency command value outside the range
between the upper and lower limiters is set.
Precautions for Correct Use
• The upper and lower limiters should be set lower than the maximum frequency. Otherwise,
warning of the inconsistency will arises.
• To set the limiters, set the upper limiter [bA102] first. Make sure that it is larger than the lower
limiter value [bA103].
• Under the restriction by the upper and lower limiters and the minimum frequency, a LIM icon
appears.
• To enable Upper Frequency limit [bA102], set [bA101] = 07: Parameter setting.
Parameter
6-5-1
Limit Frequency and Operation Commands
Item
Parameters
Data
Description
Default
data
Max. frequency
For IM
[Hb105]
For SM
(PMM)
[Hd105]
10.00 to
590.00(Hz)
Sets the max. frequency.
IM: Induction motor [AA121]=00-10
SM(PMM): Synchronous motor (permanent
magnet motor) [AA121]=11, 12
50
*1
*1. Default data when default data selection (UB-02) is set to 01.
Minimum frequency
adjustment, 1st-motor
[Hb130]
0.00 to
10.00(Hz)
Sets the min. frequency to start output.
Disabled when [AA121]=09, 10.
0.50
Frequency limit
selection, 1st-motor
[bA101]
00 to 13
00 (disabling)/01 (Ai1 terminal input)/
02 (Ai2 terminal input)/ 03 (Ai3 terminal input)/
04 (Reserved)/ 05 (Reserved)/06 (Reserved)/
07 (parameter setting)/08 (RS485)/
09 (option 1)/ 10 (option 2)/11 (option 3)/
12 (pulse string input (main body))/
13 (pulse string input (Option))
00
Upper Frequency limit,
1st-motor
[bA102]
0.00, lower
limiter of
frequency
-max. fre-
quency (Hz)
Sets the upper limit of the frequency command.
0.00
Lower Frequency limit,
1st-motor
[bA103]
0.00, start
frequency
-upper lim-
iter of fre-
quency (Hz)
Sets the lower limit of the frequency command.
Disabled when 0.00 is set.
0.00
Frequency upper limit
monitor
[dA-14]
0.00 to
590.00(Hz)
The employed upper limit of the frequency is
shown.
-
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......