7 - 75
7 Advanced Settings
High-function General-purpose Inverter RX2 Series User’s Manual
7-
5 Start
Con
dit
ion
s
7
7-5
-6 Restart after R
elea
sing Reset
(Ex.2) Frequency pull-in [bb-41]=01 to 03
(Ex.3) Restart with 0 Hz: [bb-41]=00
(Ex.4) Frequency pull-in [bb-41]=01 to 03
Precautions for Correct Use
• The restart after reset, which occurs when the inverter recovers from a reset, is the same as
the mode at power-on.
• If the frequency pull-in restart is used, the rotational direction of the output frequency is the
same as the command direction at shut-off.
• If a power failure lasts long and the inverter’s internal power supply is lost, recovery will take
place by the restart after reset instead of the restart after instantaneous power fail-
ure/under-voltage.
• In case of the 0 Hz restart, there is no wait time.
[bb-26]
Free-running
Follows [bb-41]
[RS] Reset
Operation
command
Motor speed
Restart with 0 Hz
[RS] Reset
Operation
command
Motor speed
[bb-26]
Free-running
Follows [bb-41]
[RS] Reset
Operation
command
Motor speed
Содержание RX - 2
Страница 1: ...High function General purpose Inverter RX2 Series User s Manual I620 E1 01 3G3RX2...
Страница 54: ...1 Overview 1 22 High function General purpose Inverter RX2 Series User s Manual...
Страница 136: ...2 Design 2 82 High function General purpose Inverter RX2 Series User s Manual...
Страница 592: ...8 Applied Settings 8 192 High function General purpose Inverter RX2 Series User s Manual...
Страница 754: ...11 Options 11 56 High function General purpose Inverter RX2 Series User s Manual...
Страница 794: ...12 Troubleshooting 12 40 High function General purpose Inverter RX2 Series User s Manual...
Страница 919: ......