80070107-2583ffff
Sensor [SensorElementName] has transitioned from normal to non-critical state.
Explanation:
How the CPU's are installed in the system does not match a supported configuration and may make
CPU's inaccessible to the operating system and prevent boot. [CPU Population]
May also be shown as 800701072583ffff or 0x800701072583ffff
Severity:
Warning
Alert Category:
Warning - Other
Serviceable:
Yes
CIM Information: Prefix:
PLAT and
ID:
0520
SNMP Trap ID:
60
Automatically notify Support:
No
User response:
Complete the following steps:
1.
Check the IBM ServerProven Web site to validate that the processor is a valid option for this system. If not,
remove the processor and install one that is a valid option.
2.
Verify that matching processors are installed in the correct population sequence for the system. See the system
documentation.
3.
Check the IBM support site for service bulletins or firmware updates that apply to this processor error.
4.
Replace the processor. While replacing the processor, inspect the processor socket and replace the CPU / Memory
board if the processor socket is damaged.
Related Links:
v
“Replacing a DDR3 compute book” on page 284
v
“Removing a DDR3 compute book” on page 283
80070108-1381ffff
Sensor [SensorElementName] has transitioned from normal to non-critical state.
Explanation:
The IMM has detected a Power Supply configuration error or PS 12V OC Fault or PS CSF Fault.
May also be shown as 800701081381ffff or 0x800701081381ffff
Severity:
Warning
Alert Category:
Warning - Power
Serviceable:
Yes
CIM Information: Prefix:
PLAT and
ID:
0520
SNMP Trap ID:
164
Automatically notify Support:
No
User response:
if PS 12V OC Fault is reported
Clear the over current condition.
if PS CSF Fault Fault is reported
Check if there is any other Power Supply event.
if PS ac input src
1.
Check if there is any other Power Supply event.
2.
confirm power policy and configuration setting in Web GUI.
3.
check line feeds.
4.
check documentation for correct configuration.
Related Links:
v
“Solving power problems” on page 197
v
“Installing power supplies” on page 104
80070107-2583ffff • 80070108-1381ffff
550
System x3850 X6 and x3950 X6 Types 3837 and 3839: Installation and Service Guide
Содержание X3850 X6
Страница 1: ...System x3850 X6 and x3950 X6 Types 3837 and 3839 Installation and Service Guide...
Страница 2: ......
Страница 3: ...System x3850 X6 and x3950 X6 Types 3837 and 3839 Installation and Service Guide...
Страница 138: ...120 System x3850 X6 and x3950 X6 Types 3837 and 3839 Installation and Service Guide...
Страница 225: ...25 26 27 Chapter 5 Parts listing System x3850 X6 and x3950 X6 Types 3837 and 3839 207...
Страница 1682: ...1664 System x3850 X6 and x3950 X6 Types 3837 and 3839 Installation and Service Guide...
Страница 1706: ...1688 System x3850 X6 and x3950 X6 Types 3837 and 3839 Installation and Service Guide...
Страница 1710: ...1692 System x3850 X6 and x3950 X6 Types 3837 and 3839 Installation and Service Guide...
Страница 1728: ...1710 System x3850 X6 and x3950 X6 Types 3837 and 3839 Installation and Service Guide...
Страница 1729: ......
Страница 1730: ...Part Number 00FH434 Printed in USA 1P P N 00FH434...