806f0a0c-2b82ffff
An Over-Temperature Condition has been detected on the [PhysicalMemoryElementName] on
Subsystem [MemoryElementName].
Explanation:
IMM has detected an Over Temperature Condition for Memory on Compute Book 2.
May also be shown as 806f0a0c2b82ffff or 0x806f0a0c2b82ffff
Severity:
Error
Alert Category:
Critical - Temperature
Serviceable:
Yes
CIM Information: Prefix:
PLAT and
ID:
0146
SNMP Trap ID:
0
Automatically notify Support:
No
User response:
Complete the following steps until problem is solved:
1.
Check the IMM event log for any fan or cooling related issues.
2.
Make sure that the airflow at the front and rear of the server is not obstructed and that fillers are in place and
correctly installed.
3.
Make sure that the room temperature is within operating specifications.
4.
Check IBM Support site for Service Bulletins/RETAIN tips related to an Over Temperature Condition.
5.
If the problem persists and there are no other DIMMs with the same indication, replace the DIMM.
Related Links:
v
“Server features and specifications” on page 7
v
“Removing a DDR3 compute book” on page 283
v
“Replacing a DDR3 compute book” on page 284
v
“Removing the DDR3 compute book cover” on page 218
v
“Replacing the DDR3 compute book cover” on page 220
v
“Removing a memory module” on page 239
v
“Replacing a memory module” on page 240
806f0a0c-2b830001
An Over-Temperature Condition has been detected on the [PhysicalMemoryElementName] on
Subsystem [MemoryElementName].
Explanation:
IMM determined DIMM 1 in Compute Book 3 has an Over Temperature Condition.
May also be shown as 806f0a0c2b830001 or 0x806f0a0c2b830001
Severity:
Error
Alert Category:
Critical - Temperature
Serviceable:
yes
CIM Information: Prefix:
PLAT and
ID:
0146
SNMP Trap ID:
0
Automatically notify Support:
no
User response:
Complete the following steps until problem is solved:
1.
Check the IMM event log for any fan or cooling related issues.
2.
Make sure that the airflow at the front and rear of the server is not obstructed and that fillers are in place and
correctly installed.
3.
Make sure that the room temperature is within operating specifications.
4.
Check IBM Support site for Service Bulletins/RETAIN tips related to an Over Temperature Condition.
5.
If eXFlash DIMM, make sure the eXFlash DIMM FW is updated to the latest level.
6.
If the DIMM problem persists and there are no other DIMMs with the same indication, replace the DIMM.
806f0a0c-2b82ffff • 806f0a0c-2b830001
Appendix B. Integrated management module II (IMM2) error messages
1195
Содержание X3850 X6
Страница 1: ...System x3850 X6 and x3950 X6 Types 3837 and 3839 Installation and Service Guide...
Страница 2: ......
Страница 3: ...System x3850 X6 and x3950 X6 Types 3837 and 3839 Installation and Service Guide...
Страница 138: ...120 System x3850 X6 and x3950 X6 Types 3837 and 3839 Installation and Service Guide...
Страница 225: ...25 26 27 Chapter 5 Parts listing System x3850 X6 and x3950 X6 Types 3837 and 3839 207...
Страница 1682: ...1664 System x3850 X6 and x3950 X6 Types 3837 and 3839 Installation and Service Guide...
Страница 1706: ...1688 System x3850 X6 and x3950 X6 Types 3837 and 3839 Installation and Service Guide...
Страница 1710: ...1692 System x3850 X6 and x3950 X6 Types 3837 and 3839 Installation and Service Guide...
Страница 1728: ...1710 System x3850 X6 and x3950 X6 Types 3837 and 3839 Installation and Service Guide...
Страница 1729: ......
Страница 1730: ...Part Number 00FH434 Printed in USA 1P P N 00FH434...