GREE GMV5 HR HEAT RECOVERY UNITS
243
Troubleshooting:
2.2.4.80
“H6” Drive IPM module protection of fan
Error display:
ODU mainboard will display
Error judgment condition and method:
Check the error code on nixie tube of ODU main control board. If H6 is displayed, it indicates Drive
IPM module protection of fan
Possible reason:
■Poor contact of fan UVW wire
■Fan is broken
■Fan blade is blocked (Fan blade is blocked and motor shaft is rusty)
■Fan drive board is abnormal