GREE GMV5 HR HEAT RECOVERY UNITS
165
Fault
code
Fault
Possible reasons
Solution
H7
Fan drive temperature
sensor fault
1. The fan drive board is faulty.
1. Replace the fan drive board.
H8
Fan drive IPM
over-temperature
protection
1. The fan drive board is faulty;
2. Thermal gel is not applied evenly on the
IPM module;
3. The IPM module is not screwed properly.
1. Replace the fan drive board;
2. Apply thermal gel evenly on the
IPM module;
3. Screw the IPM module properly.
H9
Variable frequency fan
out-of-step protection
1. The fan drive board is faulty.
2. The fan is damaged.
1. Replace the fan drive board.
2. Replace the fan.
HH
Fan drive DC bus high
voltage protection
1. Does the voltage of the input power cable
of the whole system exceed 410 V;
2. The fan drive board is faulty.
1. Lower the voltage of the input
power cable to the required range;
2. Replace the fan drive board.
HL
Fan drive DC bus low
voltage protection
1. Is the voltage of the input power cable of
the whole system lower than 205 V;
2. Is the fan drive board well connected with
the compressor drive board;
3. The fan drive board is faulty.
1. Elevate the voltage of the input
power cable to the required range;
2. Connect the fan drive board with
the compressor drive board
according to the wiring diagram;
3. Replace the fan drive board.
HC
Fan drive current
detection circuit fault
1. The fan drive board is faulty.
1. Replace the fan drive board.
HJ
Variable frequency fan
starting failure
1. The drive board is damaged;
2. The fan's UVW cable is not connected
properly;
3. The fan is damaged.
1. Replace the fan drive board;
2. Reconnect the fan's UVW cable;
3. Replace the fan.
2.1.2 System faults
(1) System exhaust temperature exception
Fault
code
Fault
Possible reasons
Solution
Primary reason
Secondary reason
Tertiary reason
Description
Confirmation
method
Description
Confirmation
method
Description
Confirmation
method
E4
High exhaust
temperature
protection
1. The stop
valve of the
ODU is not
fully opened
as required.
——
——
——
——
Manual check
Fully open
the stop
valve.
2. The IDU's
electronic
expansion
valve is not
working
properly.
When the IDU
is working in
the cooling
mode and the
electronic
expansion
valve is
opened to
2000PLS, the
exhaust
temperature of
the IDU's coil
is more than
15°C
(
27
°F)
higher than
the intake
temperature;
2.1 The
controlling of
electronic
expansion
valve by
main board
of indoor unit
is abnormal.
Reset the IDU.
Listen to the
sound and
touch the tube
to see if the
electronic
expansion
valve is reset.
If it is set, it is
normal.
Otherwise, it is
faulty.
2.1.1 The
control wire
of the
electronic
expansion
valve is not
connected to
the main
board.
Manual check
Connect the
electronic
expansion
valve's
control wire
to the main
board.
2.1.2 The
control wire
that
connects the
electronic
expansion
valve to the
main board
is broken.
Manual check
Repair or
replace the
control wire
of the
electronic
expansion
valve.
Содержание GC201808-III
Страница 36: ...GREE GMV5 HR HEAT RECOVERY UNITS 32 Circuit diagram of GMV Q144WM B1 F U Circuit diagram of GMV Q168WM B1 F U ...
Страница 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Страница 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Страница 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Страница 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Страница 314: ...GREE GMV5 HR HEAT RECOVERY UNITS 310 4 Loosen the screws on the compressor drive as shown in the figure below ...
Страница 362: ...JF00302879 ...