GREE GMV5 HR HEAT RECOVERY UNITS
264
Troubleshooting:
Make sure the IDUs connected with one wired controller belong to the same series.
2.2.4.105
“LC” Mismatch of IDU and ODU models
Error display:
IDU wired controller and IDU receive light board will display
Error judgment condition and method:
When some IDUs or devices which cannot be identified by some ODUs are installed in the system,
mismatch error of IDU and ODU models will occur.
Possible reason:
■Mismatch of IDU and ODU
Troubleshooting:
When some IDUs or devices which cannot be identified by some ODUs are installed in the system
(E.g. floor heating device is installed in modular DC inverter multiple VRF system), the error will occur.
Please remove the relevant IDU devices or replace the ODU with suitable model.
2.2.4.106
“n0” System energy-saving operation setting status
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will
display
Error judgment condition and method:
This code is function setting status code, which indicates that the system has entered energy-saving
setting status.
“00” is the control with priority of comfort; “01” is the control with priority of energy savings,
in which energy savings can reach 15%.
Possible reason:
——
Troubleshooting:
status code, no troubleshooting.
2.2.4.107
“n2” Upper limit setting status of IDU&ODU capacity configuration ratio
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will
display
Error judgment condition and method:
This code is function setting status code, which indicates that the system has entered upper limit
setting status of IDU&ODU capacity configuration ratio.
Possible reason:
——
Troubleshooting:
status code, no troubleshooting.
2.2.4.108
“n4” Limit setting status of max output capacity
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will
display
Содержание GC201808-III
Страница 36: ...GREE GMV5 HR HEAT RECOVERY UNITS 32 Circuit diagram of GMV Q144WM B1 F U Circuit diagram of GMV Q168WM B1 F U ...
Страница 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Страница 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Страница 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Страница 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Страница 314: ...GREE GMV5 HR HEAT RECOVERY UNITS 310 4 Loosen the screws on the compressor drive as shown in the figure below ...
Страница 362: ...JF00302879 ...