GREE GMV5 HR HEAT RECOVERY UNITS
172
Fault
code
Fault
Possible reasons
Solution
Primary reason
Secondary reason
Tertiary reason
Description
Confirmation
method
Description
Confirmation
method
Description
Confirmation
method
E1
High
pressure
protection
6. The fan
is not
working
properly.
A. The
ODU's fan
does not
work in the
cooling
mode. B. The
IDU's motor
does not
work in the
heating
mode.
6.1 The
IDU's fan is
faulty.
Manual
check
6.1.1 The power
cable
connecting the
motor and main
board is loose.
Manual
check
Reconnect the
motor with the
power cable.
6.1.2 The
electric capacity
is not connected
or is damaged.
Manual
check
Connect or
replace the
electric capacity.
6.1.3 The motor
is damaged.
Other
reasons
Replace the
motor.
6.2 The
ODU's fan is
faulty.
Manual
check
6.2.1 The fan
motor is not
properly
connected with
the control board
of the motor with
the power cable.
Manual
check
Reconnect it
properly.
6.2.2 The fan
motor is not
properly
connected with
the control board
of the motor with
the signal
feedback cable.
Manual
check
Reconnect it
properly.
6.2.3 The control
board of the
fan's motor is
damaged.
Manual
check
Replace the
control board of
the motor.
6.2.4 The main
board of the
fan's motor is
damaged.
Other
reasons
Replace the
motor.
7. Too
much
refrigerant
Other
reasons
Incorrect
quantity of
refrigerant is
injected.
——
——
——
Check the
necessary
amount of
refrigerant and
discharge
unneeded
refrigerant slowly
via the stop valve
of the fluid pipe.
JL
Low high
pressure
protection
1. The
ambient
temperatur
e exceeds
the range.
——
1.1 The
outdoor
ambient
temperature
in the cooling
mode is
lower than
-10°C
(
14
°F)
.
Measure the
outdoor
ambient
temperature.
——
——
It is a normal
phenomenon
caused by the
protection
function.
Содержание GC201808-III
Страница 36: ...GREE GMV5 HR HEAT RECOVERY UNITS 32 Circuit diagram of GMV Q144WM B1 F U Circuit diagram of GMV Q168WM B1 F U ...
Страница 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Страница 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Страница 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Страница 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Страница 314: ...GREE GMV5 HR HEAT RECOVERY UNITS 310 4 Loosen the screws on the compressor drive as shown in the figure below ...
Страница 362: ...JF00302879 ...