GREE GMV5 HR HEAT RECOVERY UNITS
119
After 10 seconds, the system quits this mode and restores the normal operation mode.
NOTE: This function only needs to be set on the master system, which is the system with the
centralized control address SA2 DIP switch being "00000". For details, see the "Centralized Control
Address DIP Switch (SA2_Addr-CC)" section.
3.4 Function Query Operations
Step 1: Open the commissioning window of the master unit panel.
Step 2: Power on the entire unit.
Step 3: Press "SW4" on the master unit to enter the query status.
Step 4: Select a function to be queried by pressing "SW1 (UP)" or "SW2 (DOWN)" on the master
unit. By default, the A7 outdoor silent mode is displayed for query.
For example, select the A6 unit cooling/heating function. The display is as follows:
LED1
LED2
LED3
Function Code
Display Mode
ODU Function
Mode Code
Display Mode
ODU Function
Mode Code
Display Mode
A6
On
nA
On
nA
On
ED1
LED2
LED3
Function Code
Display Mode
Current
Progress/Mode
Display Mode
Current Status
Display Mode
n8
Blinking
00
Blinking
00
Blinking
Press "SW7" and select the IDU project number query on the master unit. The master unit is
displayed as follows. Other modules are displayed in normal status.
LED1
LED2
LED3
Function Code
Display Mode
Current
Progress/Mode
Display Mode
Current Status
Display Mode
n8
On
00
On
00
On
Regardless of the current display status of wired controllers or display panels of all IDUs, the current
display status is all switched to the IDU project number. However, it does not influence the settings and
operation status of outdoor and IDUs.
On the master unit, press "SW6" to return to the upper level. The IDU retains the project number
display status.
On the master unit, press and hold "SW6" to quit the address display status for all IDUs and return
to the upper level.
If no quit button operations are performed on the master unit for 30 minutes, the function setting
automatically quits and the unit restores the current status.
Step 6: If the n8 IDU address query is selected, the display is as follows:
LED1
LED2
LED3
Function Code
Display Mode
Number of IDUs
(Thousands-place
Hundreds- place)
Display Mode
Number of IDUs
(Tens-place
Ones-place)
Display Mode
n9
On
00
On
00
Blinking
The digital LED2 displays the number of IDUs (thousands-place hundreds-place) and the digital
LED3 displays the number of IDUs (tens-place ones place). For example, if the number of IDUs is 75,
Содержание GC201808-III
Страница 36: ...GREE GMV5 HR HEAT RECOVERY UNITS 32 Circuit diagram of GMV Q144WM B1 F U Circuit diagram of GMV Q168WM B1 F U ...
Страница 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Страница 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Страница 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Страница 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Страница 314: ...GREE GMV5 HR HEAT RECOVERY UNITS 310 4 Loosen the screws on the compressor drive as shown in the figure below ...
Страница 362: ...JF00302879 ...