![Gree GC201808-III Скачать руководство пользователя страница 153](http://html.mh-extra.com/html/gree/gc201808-iii/gc201808-iii_service-manual_2260766153.webp)
GREE GMV5 HR HEAT RECOVERY UNITS
149
Step 4: On the engineering debugging page, click “Startup” button to start engineering debugging;
press “Stoppage” button to pause the engineering debugging;
Step 5: Once it entered the engineering debugging, Portable Commissioning Tool will display
current progress of engineering debugging (step#). As for step 3, 4, 8 and 12,
it needs to
click “OK” button to enter into the next step debugging. “Skip” can be selected for step 10.
Detailed information check is available for step 3, 4, 5, 6 and 7.
Step 6: Once engineering debugging is finished, the outdoor unit displays 01 AC or AH OF (or error
code when there’s malfunction; on is displayed when the unit is displayed)
Warning: After finishing operating this product, the wiring of air conditioner must be resumed.
Otherwise, it may affect the actual operation of user!
3.3.4 Operations after Commissioning
Sort and save data. Make detailed records of exceptions and troubleshooting methods during
commissioning for later maintenance and query. At last, make a commissioning report and hand it over
to users.
3.3.5 Precautions to Let Users Know after Commissioning
(1) Let users know where the master IDU is located and stick a label to the master IDU. Tell users
that modes of other IDUs are limited by the mode of master IDU.
(2) An ODU that has been in power-off status for more than 24 hours should be preheated for more
than eight hours before startup to prevent damaging compressors.
Содержание GC201808-III
Страница 36: ...GREE GMV5 HR HEAT RECOVERY UNITS 32 Circuit diagram of GMV Q144WM B1 F U Circuit diagram of GMV Q168WM B1 F U ...
Страница 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Страница 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Страница 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Страница 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Страница 314: ...GREE GMV5 HR HEAT RECOVERY UNITS 310 4 Loosen the screws on the compressor drive as shown in the figure below ...
Страница 362: ...JF00302879 ...