GREE GMV5 HR HEAT RECOVERY UNITS
235
Troubleshooting:
2.2.4.70
“FE” Compressor 4 current sensor error
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will
display
Error judgment condition and method:
Sample the AD value of current sensor through detecting circuit and judge the range of AD value; if
the sampled AD value exceeds upper limit and lower limit in 3 seconds continuously, report the error.
Possible reason:
■Poor contact between circuit sensor and terminal in mainboard interface
■Small board of circuit sensor is abnormal
■Detecting circuit is abnormal
Содержание GC201808-III
Страница 36: ...GREE GMV5 HR HEAT RECOVERY UNITS 32 Circuit diagram of GMV Q144WM B1 F U Circuit diagram of GMV Q168WM B1 F U ...
Страница 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Страница 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Страница 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Страница 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Страница 314: ...GREE GMV5 HR HEAT RECOVERY UNITS 310 4 Loosen the screws on the compressor drive as shown in the figure below ...
Страница 362: ...JF00302879 ...