GREE GMV5 HR HEAT RECOVERY UNITS
220
2.2.4.56
“E3” System low pressure protection
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will
display
Error judgment condition and method:
Test compressor suction pressure through low pressure sensor. When pressure value is lower than
-41
°C
, the unit will stop for protection.
Possible reason:
■Cut-off valve of ODU is not fully opened;
■Low pressure sensor is abnormal;
■Outdoor or indoor fan is not working properly;
■IDU filter or air duct is blocked (cooling mode);
■Ambient temperature is too low;
■Refrigerant charging amount is insufficient;
■System pipeline is blocked;