GREE GMV5 HR HEAT RECOVERY UNITS
95
(5) If the pressure must be kept for a long time, decrease the pressure to 0.5 MPa or lower. High
pressure for a long time may cause leakage at the welding point or safety hazard.
(6) Before performing the air-tightness test to the refrigerant pipes, do not conduct insulation or
wrapping at the welding or flaring opening joints of the IDU. The pressure must be increased
simultaneously for pipes on outdoor sides and cannot be increased for pipes on one side.
Before performing the air-tightness test, do not conduct insulation or wrapping at the welding
joints
,
Otherwise, leak source cannot be detected quickly.
2 VACUUMIZATION AND DESICCATION
FOR THE SYSTEM
2.1 Requirements on the Vacuum Pump
The vacuum pump for different refrigerant systems cannot be the same.
The ultimate vacuum degree of the vacuum pump should reach -0.1 Mpa.
The air discharge capacity of the vacuum pump must be greater than 4 L/S.
The precision of the vacuum pump must be greater than 0.02 mmHg.
The system vacuum pump must be equipped with a check valve.
2.2 Procedure and Precautions for Vacuumization and
Desiccation
2.2.1 Procedure
(1) Before vacuumization, ensure that the stop valves of the gas and liquid pipes are turned off.
(2) Use the perfusing duct to connect the regulator valve and vacuum pump to detection
connectors of the gas pipe and liquid pipe.
(3) Vacuumize for 4 hours and check whether the vacuum degree reaches -0.1 MPa or more. If not,
leakage may exist. Perform leakage check again. If no leakage exists, continue to vacuumize
for 2 hours.
(4) If the vacuum degree cannot be kept after vacuumization is performed for twice, there may be
water in the pipe when it is confirmed that no leakage exists. In this case, discharge water by
Содержание GC201808-III
Страница 36: ...GREE GMV5 HR HEAT RECOVERY UNITS 32 Circuit diagram of GMV Q144WM B1 F U Circuit diagram of GMV Q168WM B1 F U ...
Страница 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Страница 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Страница 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Страница 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Страница 314: ...GREE GMV5 HR HEAT RECOVERY UNITS 310 4 Loosen the screws on the compressor drive as shown in the figure below ...
Страница 362: ...JF00302879 ...