GREE GMV5 HR HEAT RECOVERY UNITS
242
Troubleshooting:
2.2.4.79
“H5” Inverter fan overcurrent protection
Error display:
ODU mainboard will display
Error judgment condition and method:
Check the error code on nixie tube of ODU main control board. If H5 is displayed, it indicates
inverter fan overcurrent protection
Possible reason:
■Poor contact of fan UVW wire
■Fan is broken
■Fan blade is blocked (Fan blade is blocked and motor shaft is rusty)
■Fan drive board is abnormal