GREE GMV5 HR HEAT RECOVERY UNITS
133
Progress Description for Commissioning Phases
——
Commissioning Code Progress Code
Status Code
Meaning
Progress
LED1
LED2
LED3
Code
Display
Status
Code
Display
Status
Code
Display
Status
04_Indoor unit
quantity confirmation
db
On
04
On
01-80
Blinking
LED3 displays the IDU quantity,
which should be manually
confirmed.
db
On
04
On
OC
On
The system confirms the IDU
quantity and automatically enters
the next step.
05_Internal
communication
detection for basic
modules
db
On
05
On
C2
On
The system detects
communication failure between
master unit and inverter
compressor driver.
db
On
05
On
C3
On
The system detects
communication failure between
master unit and inverter fan
driver.
db
On
05
On
CH
On
The rated capacity ratio is
over-high between IDUs and
ODUs.
db
On
05
On
CL
On
The rated capacity ratio is
over-low between IDUs and
ODUs.
db
On
05
On
OC
On
The system completes detection
and automatically enters the next
step.
06_Internal
component detection
for basic modules
db
On
06
On
Corresponding
fault code
On
The system detects component
failure of ODU.
db
On
06
On
OC
On
The system detects that no ODU
component fails and
automatically enters the next
step.
07_Component
detection for IDU
db
On
07
On
XXXX/
Corresponding
fault code
On
The system detects component
failure of IDU. "XXXX" indicates
the project number of the faulty
IDU. The corresponding fault
code is displayed after three
seconds. For example, if a d5
fault occurs on IDU 100, LED3
will circularly display "01", "00"
(two seconds later), and "d5"
(two seconds later).
db
On
07
On
OC
On
The system detects that no IDU
component fails and
automatically enters the next
step.
08_Compressor
preheating
confirmation
db
On
08
On
U0
On
The system gives a prompt if the
compressor preheating period is
less than eight hours.
db
On
08
On
OC
On
The system detects that the
compressor preheating period is
more than eight hours and
automatically enters the next
step.
09_Pre-startup
refrigerant detection
db
On
09
On
U4
On
The system detects insufficient
refrigerants and stops to balance
the pressure lower than 0.3 MPa.
Содержание GC201808-III
Страница 36: ...GREE GMV5 HR HEAT RECOVERY UNITS 32 Circuit diagram of GMV Q144WM B1 F U Circuit diagram of GMV Q168WM B1 F U ...
Страница 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Страница 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Страница 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Страница 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Страница 314: ...GREE GMV5 HR HEAT RECOVERY UNITS 310 4 Loosen the screws on the compressor drive as shown in the figure below ...
Страница 362: ...JF00302879 ...