GREE GMV5 HR HEAT RECOVERY UNITS
84
①
Indoor Unit ground Lines are required for preventing electrical shock accident during current
leakage, Communication disorder by noise effect and motor current leakage (without
connection to pipe).
②
Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately
from the power supply.
③
Install the main switch that can interrupt all the power sources in an integrated manner because
this system consists of the equipment utilizing the multiple power sources.
④
If there exists the possibility of reversed phase, lose phase, momentary blackout or the power
goes on and off while the product is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
NOTE:
The maximum number of connected IDUs (n) is determined based on the capacity of the ODU. For
details, see the description on unit capacity configuration.
(2) External Connection for Modularly Connected Units
Содержание GC201808-III
Страница 36: ...GREE GMV5 HR HEAT RECOVERY UNITS 32 Circuit diagram of GMV Q144WM B1 F U Circuit diagram of GMV Q168WM B1 F U ...
Страница 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Страница 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Страница 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Страница 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Страница 314: ...GREE GMV5 HR HEAT RECOVERY UNITS 310 4 Loosen the screws on the compressor drive as shown in the figure below ...
Страница 362: ...JF00302879 ...