Step 2: Turn on the valves for the liquid and gas pipes of each module completely. For the modular
unit, the oil-equalizing valve of each module also needs to be turned on.
Step 3: Make the system to run in commissioning mode via the commissioning software or the main
board of the ODU. (For details, see the description on commissioning.)
Step 4: When the commissioning step goes to refrigerant perfusion, turn on the valve of the
refrigerant tank and perfuse the remaining quantity (m`).
Step 5: After all refrigerant is perfused, turn off valve of the refrigerant tank and wait till
commissioning is automatically is completed for the system.
Step 6: Remove the pressure gauge to finish refrigerant perfusion.
Because R410A is a mixture of refrigerant, therefore, it must be charged in a liquid form.
Otherwise, unit will not work stably and effectively.
Do not expose the R410A refrigerant tank to direct sunlight. Otherwise, the internal pressure
may get too high and cause explosion.
Pipeline for the R410A refrigerating system must have relevant valid certificates.
During welding, avoid overheating the pipeline.
System must not filled with refrigerant other than R410A.
Pipe to be vacuumed : gas pipe, water pipe, common pipe
If the refrigerant amount is not exact, it may not operate properly.
If additionally bottled refrigerant amount is over ±10%, condenser burning or insufficient indoor
unit performance may be caused.
Содержание GC201808-III
Страница 36: ...GREE GMV5 HR HEAT RECOVERY UNITS 32 Circuit diagram of GMV Q144WM B1 F U Circuit diagram of GMV Q168WM B1 F U ...
Страница 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Страница 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Страница 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Страница 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Страница 314: ...GREE GMV5 HR HEAT RECOVERY UNITS 310 4 Loosen the screws on the compressor drive as shown in the figure below ...
Страница 362: ...JF00302879 ...