GREE GMV5 HR HEAT RECOVERY UNITS
213
Troubleshooting:
2.2.4.46
“d6” Outlet pipe temperature sensor error
Error display:
IDU wired controller and IDU receive light board will display
Error judgment condition and method:
Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge
the range of AD value. If the sampling AD value exceeds upper limit and lower limit in 5 seconds
continuously, report the error
Possible reason:
■Poor contact between outlet pipe temperature sensor and terminal in mainboard interface
■Outlet pipe temperature sensor is abnormal
■Detecting circuit is abnormal