GREE GMV5 HR HEAT RECOVERY UNITS
159
conflict, may occur on different cooling systems. In such case, set project numbers of each system and
solve the fault as follows:
(1) Project number conflict:
When multiple systems are controlled in a centralized way, if two or more IDUs share the same
project number, the engineer number conflict occurs. In that case, IDUs cannot be switched to varied
modes or be turned on or off. The whole device cannot be started before the conflict is solved. The
commissioning software will show the following page:
Figure 1