GREE GMV5 HR HEAT RECOVERY UNITS
37
Change Indoor Unit type:
Installation position should be over 6.6ft from the floor (Wall mounted type
→
Cassette type)
Adoption of ventilation system:
Choose ordinary ventilation system or building ventilation system
Limitation in piping work:
Prepare for earthquake and thermal stress
8 UNIT OPERATING TEMPERATURE
Cooling operation
Ambient temperature: -5°C(23°F)~52°C(125.6°F)
Heating operation
Ambient temperature: -20°C(-4°F)~24°C(75.2°F)
Heat recovery operation
Ambient temperature:-10°C(14°F)~20°C(68°F)
In the case of a full fresh air conditioning IDU, the unit operating temperature is as follows:
Cooling operation
Ambient temperature: 16°C
(
60.8
°
F)
~45°C
(
113
°
F)
Heating operation
Ambient temperature: -7°C
(
19.4
°
F)
~16°C
(
60.8
°
F)
If unit operates out of the above range, it may not work stably and components may even be
damaged.