GREE GMV5 HR HEAT RECOVERY UNITS
34
5 OPTIONAL ACCESSORIES
GMV5 series VRF units support the following optional accessories:
Export Model
Remark
Manifold
ODU
ML01R
For model selection, refer to Pipe
Selection.
Mode
Converter
FQ01Na/A, FQ02Na/A, FQ03Na/A, FQ04Na/A,
FQ05Na/A,FQ06Na/A , FQ07Na/A
IDU
FQ01A/A
Remote-control Receiver Board
JS05
Applicable for air-duct-type IDUs.
Commissioning Remote
Controller
YV1L1
Provides the commissioning functions
for function settings of IDUs.
Commissioning Software
DE40-33/A(C)
Applicable for units that support CAN
bus communication technology.
Remote Monitoring
System
Software
FE30-24/DF(B)
Applicable for units that support CAN
bus communication technology.
Gateway
ME30-24/DF(B)
NOTICE!
Contact local sales company for optional accessories.
6 BASIC REQUIREMENT FOR PIPE
CONNECTION
(1) Outdoor units adopt the modular combination design of individual cooling system, that is, units
are connected by using pipes in parallel during installation. The tubing system used among
modules includes Liquid pipes, high pressure gas pipes and low pressure gas pipes.
Functions of oil check valve: During after-sale maintenance, the oil check valve can be used to
extract lubricating oil samples, which are further detected to analyze the oil quality in the
system. The oil check valve can also serve as the inlet for lubricating oil charging. Before
extracting lubricating oil from the system, stop the system for at least 12 hours and release
refrigerant. Do not extract oil until system’s pressure drops to 0.05MPa (7.25psi) or below;
otherwise, overheat oil may burn the operator.
Functions of low-pressure check valve: It is mainly used for low pressure detection of the
system and refrigerant charging during after-sale maintenance.
Содержание GC201808-III
Страница 36: ...GREE GMV5 HR HEAT RECOVERY UNITS 32 Circuit diagram of GMV Q144WM B1 F U Circuit diagram of GMV Q168WM B1 F U ...
Страница 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Страница 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Страница 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Страница 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Страница 314: ...GREE GMV5 HR HEAT RECOVERY UNITS 310 4 Loosen the screws on the compressor drive as shown in the figure below ...
Страница 362: ...JF00302879 ...