Suppose the Pipeline charging amount A=Σ Liquid pipe length × refrigerant charging amount of
every 1m (39.37inch) liquid pipe=25kg (55.1 pounds)
Total refrigerant charging amount R=25+12=37kg (55.1+26.4=81.5pounds).
After confirming that there is no leakage from the system, when the compressor is not in operation,
charge additional R410A with specified amount to the unit through the filling opening of the liquid pipe
valve of the outdoor unit. If required additional refrigerant cannot be quickly filled for increase of pressure
in the pipe, set the unit at cooling startup and then fill the refrigerant from gas valve of outdoor unit. If
ambient temperature is low, the
unit can’t be set to cooling mode but heating mode.
Refrigerant amount must be calculated and treated by strictly following the above methods.
Otherwise, system will not work normally and compressor may even be damaged.
Rated capacity configuration ratio C of outdoor/indoor unit = Rated Cooling capacity sum of
indoor units/Rated Cooling capacity sum of outdoor units
If all the indoor units are GMV-NDX series fresh air indoor units, the added refrigerant quantity
B for every module is 0 kg
(
Pound
)
.
2 METHOD FOR PERFUSING REFRIGERANT
Refrigerant perfusion for the VRF system is classified into pre-perfusion and perfusion during
running.
2.1 Refrigerant Pre-perfusion
Step 1: Connect the high pressure gauge pipe to the detection opening of the liquid pipe, and the
medium gauge pipe to the vacuum pump. Power on the vacuum pump to perform vacuumization and
desiccation.
Step 2: After vacuumization and desiccation are finished, turn off valves of the high pressure gauge
and low pressure gauge. Disconnect the medium gauge pipe from the vacuum pump and connect it to
the refrigerant tank.
Step 3: Properly loosen the joint between the medium gauge pipe and the pressure gauge and
slightly turn on the valve of the refrigerant tank. Vacuumize the medium gauge pipe. After that, fasten the
joint and turn on the valve of the refrigerant tank completely.
Step 4: If the refrigerant tank is not equipped with a siphon, reverse the refrigerant tank and place it
on the electronic scale. Then record the current weight (m1). If the refrigerant tank is equipped with a
siphon, record the current weight (m1) directly.
Содержание GC201808-III
Страница 36: ...GREE GMV5 HR HEAT RECOVERY UNITS 32 Circuit diagram of GMV Q144WM B1 F U Circuit diagram of GMV Q168WM B1 F U ...
Страница 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Страница 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Страница 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Страница 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Страница 314: ...GREE GMV5 HR HEAT RECOVERY UNITS 310 4 Loosen the screws on the compressor drive as shown in the figure below ...
Страница 362: ...JF00302879 ...