GREE GMV5 HR HEAT RECOVERY UNITS
255
display
Error judgment condition and method:
Check the operation current of compressor through current sensor or circuit. When current exceeds
the limit, the unit will stop for protection.
Possible reason:
■System parameters are abnormal;
■Drive module is abnormal;
■Compressor is abnormal;
Troubleshooting:
2.2.4.95
“J7” Gas-mixing protection of 4-way valve
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will