GREE GMV5 HR HEAT RECOVERY UNITS
157
NOTE1:
If the enquired IDU is normal, no fault code will be displayed in the temperature area; if the
unit indoor has multiple faults, fault codes will be displayed in the temperature area at an interval of 3
seconds.
NOTE2:
Press the “ON/OFF” button on the interface of IDU project number and fault enquiry to exist
the parameter enquiry interface.
2 Exception Analyzing and Troubleshooting
2.1 Form analyzing
2.1.1 Control
Fault code
Fault
Possible reasons
Solution
F0
Faults in the
ODU's main board
(such as memory
and address chip
exceptions)
1) The clock chip on the main
board is damaged.
2) The memory chip on the main
board is damaged.
3) The address chip on the main
board is damaged.
1) Replace the small CPU board.
2) Replace the control board.
3) Replace the control board.
FC
Faults in the
constant
frequency
compressor's
current sensor
1) The constant-frequency
compressor is not started.
2) The current detection board is
faulty.
3) The main board's detection
circuit is faulty.
1) If the compressor is not started, check if the
AC contact is closed. If not, replace the AC
contact.
If the connection is loose, reconnect it;
2) Replace the current detection board.
3) Replace the main board.
U2
Wrong outdoor
capacity code
setting
1) The capacity code is wrong.
2) The dial component is faulty.
1)Modify the capacity code setting.
2)Replace the main board.
U3
Power phase
sequence
protection
1) The three-phase power cable
is not connected correctly.
2) The main board's detection
circuit is faulty.
1) Check connection of the power cable.
2) Replace the control board.
UL
Wrong emergency
operation dial
code
1) The dial setting is wrong.
2) The dial component is faulty.
1) Modify the dial setting.
2) Replace the main board.
C0
Communication
failure between
indoor and ODUs
and IDU's
communicator
1) The communication cable is
not connected.
2) The communicator is
disconnected.
3) The communication cable is
poorly connected.
4) The communicator controller
is faulty.
If C0 is not displayed on the control board of the
ODU, check the network between the IDU and
communicator. If C0 is displayed, check the
network between the IDUs and ODUs and
between the IDU and communicator as follows:
1) Check if the cables connecting the control
board of the ODU and the IDU and connecting
the IDU and communicator are loose. If yes,
reconnect them;
2) Check if the cables connecting the control
board and IDU and connecting the IDU and
communicator are broken. If yes, replace the
cables;
3) Check the contact of the communication
cables;
4) Replace the control board. If the fault is solved,
the control board is faulty. Replace the IDU. If the
fault is solved, the IDU is faulty.
Содержание GC201808-III
Страница 36: ...GREE GMV5 HR HEAT RECOVERY UNITS 32 Circuit diagram of GMV Q144WM B1 F U Circuit diagram of GMV Q168WM B1 F U ...
Страница 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Страница 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Страница 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Страница 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Страница 314: ...GREE GMV5 HR HEAT RECOVERY UNITS 310 4 Loosen the screws on the compressor drive as shown in the figure below ...
Страница 362: ...JF00302879 ...