GREE GMV5 HR HEAT RECOVERY UNITS
203
■Connected wired controller quantity or address setting is improper
■Controller is abnormal
Troubleshooting:
If C0 isn’t displayed on the ODU main control board, please check the network between IDU and
wired controller; if ODU main control board, IDU light board and wired controller all report C0, please
check the network between ODU and IDU and the network between IDU and wired controller; if only
wired controller reports C0, please check the network between IDU and wired controller and the wired
controller quantity and address settings.
2.2.4.28
“C2” main control and inverter compressor drive communication error
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will