GREE GMV5 HR HEAT RECOVERY UNITS
300
Note:
Before replacing the faulty parts, make sure to block their openings with tapes. They should
be kept intact for further analysis.
Note:
Volumes of oils drawn out from the oil separator, and gas separator should be recorded. After
faulty compressors and parts are replaced, you should fill new oils of equivalent amount into the
compressors and parts.
Step 6: Clear pipeline system.
Check pipelines for abnormalities. Charge nitrogen into the main pipeline and clear the pipeline
system.