GREE GMV5 HR HEAT RECOVERY UNITS
168
Fault
code
Fault
Possible reasons
Solution
Primary reason
Secondary reason
Tertiary reason
Description
Confirmation
method
Description
Confirmation
method
Description
Confirmation
method
temperature of
the
corresponding
liquid-air
separator is
more than
1°C
(
1.8
°F)
lower than the
low-pressure
saturation
temperature
and the
difference
between the
compressor's
exhaust
temperature or
cover
temperature
and the
high-pressure
temperature is
smaller than
10°C
(
18
°F)
.
valve of
the
subcooler
is faulty.
reset.
If it is set, it
is normal.
Otherwise,
it is faulty.
1.2.2 The
control
wire that
connects
the
electronic
expansion
valve to
the main
board is
broken.
Manual
check
Repair or
replace the
control wire
of the
electronic
expansion
valve.
1.3 The
body of the
electronic
expansion
valve is
not
working
properly.
Other
reasons
1.3.1
Affected
by
impurities
in the
system
——
Clean the
system and
clear the
impurities.
Replace the
body of the
electronic
expansion
valve.
1.3.2 The
body of the
valve is
faulty.
——
Replace the
body of the
electronic
expansion
valve.
Fault
code
Fault
Possible reasons
Solution
Primary reason
Secondary reason
Tertiary reason
Description
Confirmation
method
Description
Confirmation
method
Description
Confirmation
method
E2
Low
exhaust
temperature
protection
2. The IDU's
electronic
expansion
valve is not
working
properly
When the
system is
working in the
cooling mode
and the ODU's
electronic
expansion
valve is
opened to
200PLS, the
exhaust
temperature of
the IDU's coil
is more than
1°C°
(
1.8
°F)
lower than the
intake pipe's
temperature
2.1 The
controlling of
electronic
expansion
valve by
main board
of indoor unit
is abnormal.
Reset the IDU.
Listen to the
sound and
touch the tube
to see if the
electronic
expansion
valve is reset.
If it is set, it is
normal.
Otherwise, it is
faulty.
2.1.1 The
control wire
of the
electronic
expansion
valve is not
connected to
the main
board.
Manual
check
Connect the
electronic
expansion
valve's control
wire to the
main board.
2.1.2 The
control wire
that
connecting
the
electronic
expansion
valve to the
main board
is broken.
Manual
check
Repair or
replace the
control wire of
the electronic
expansion
valve.
Содержание GC201808-III
Страница 36: ...GREE GMV5 HR HEAT RECOVERY UNITS 32 Circuit diagram of GMV Q144WM B1 F U Circuit diagram of GMV Q168WM B1 F U ...
Страница 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Страница 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Страница 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Страница 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Страница 314: ...GREE GMV5 HR HEAT RECOVERY UNITS 310 4 Loosen the screws on the compressor drive as shown in the figure below ...
Страница 362: ...JF00302879 ...