GREE GMV5 HR HEAT RECOVERY UNITS
205
Troubleshooting:
2.2.4.30
“C4” IDU missing error
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will
display
Error judgment condition and method:
If ODU hasn
’t received inverter fan drive board data in continuous 30s, report the error.
Possible reason:
■Communication wire is in poor connection
■Power supply of IDU is cut off
■IDU mainboard is abnormal
Troubleshooting: