GREE GMV5 HR HEAT RECOVERY UNITS
186
Fault
code
Fault
Possible reasons
Solution
Primary reason
Secondary reason
Tertiary reason
Description
Confirmation
method
Description
Confirmation
method
Description
Confirmation
method
6.2.3 The
control board
of the fan's
motor is
damaged.
Manual check
Replace the
control board of
the motor.
6.2.4 The
main board
of the fan's
motor is
damaged.
Other reasons
Replace the
motor.
7. Too much
refrigerant
Other
reasons
Incorrect
quantity of
refrigerant is
injected.
——
——
——
Check the
necessary
amount of
refrigerant and
discharge
unneeded
refrigerant
slowly via the
stop valve of
the fluid pipe.
JL
Low high
pressure
protection
1. The
ambient
temperature
exceeds the
range.
——
1.1 The
outdoor
ambient
temperature
in the
cooling
mode is
lower than
-10°C.
Measure the
outdoor ambient
temperature.
——
——
It is a normal
phenomenon
caused by the
protection
function.
1.2 The
indoor
ambient
temperature
in the
heating
mode is
lower than
5°C.
Measure the
temperature of
the unit's return
air.
——
——
It is a normal
phenomenon
caused by the
protection
function.
2. Not
enough
refrigerant
——
Locate the leak
and inject
refrigerant.
Содержание GC201808-III
Страница 36: ...GREE GMV5 HR HEAT RECOVERY UNITS 32 Circuit diagram of GMV Q144WM B1 F U Circuit diagram of GMV Q168WM B1 F U ...
Страница 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Страница 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Страница 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Страница 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Страница 314: ...GREE GMV5 HR HEAT RECOVERY UNITS 310 4 Loosen the screws on the compressor drive as shown in the figure below ...
Страница 362: ...JF00302879 ...