GREE GMV5 HR HEAT RECOVERY UNITS
295
pad NV (make sure the moisture proof tape is removed). In normal cases, the multimeter
should read 0.39±0.3 V. If it is “0” or infinitely great, the IPM module is faulty.
(7) As shown in the figure below, put the black test probe to pad W (RD) and the red test probe to
pad NW (make sure the moisture proof tape is removed). In normal cases, the multimeter
should read 0.39±0.3 V. If it is “0” or infinitely great, the IPM module is faulty.
2.1.2 Precondition: Units cannot be normally started
Step 1:
Disconnect the power supply of the units and open the electric junction box of the compressor to
see whether wiring of the compressor is intact.
Step 2:
Measure resistance between two wiring terminals (U, V, W). The resistance value range should be
0.5~2.0 Ω.
Measure
resistance
between two
wiring terminals
using a
multimeter
Measure the
resistance to earth
of each wiring
terminal one after
another
Содержание GC201808-III
Страница 36: ...GREE GMV5 HR HEAT RECOVERY UNITS 32 Circuit diagram of GMV Q144WM B1 F U Circuit diagram of GMV Q168WM B1 F U ...
Страница 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Страница 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Страница 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Страница 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Страница 314: ...GREE GMV5 HR HEAT RECOVERY UNITS 310 4 Loosen the screws on the compressor drive as shown in the figure below ...
Страница 362: ...JF00302879 ...