GREE GMV5 HR HEAT RECOVERY UNITS
204
display
Error judgment condition and method:
If ODU hasn
’t received inverter compressor drive board data in continuous 30s, report the error.
Possible reason:
■Communication wire between ODU mainboard inside module and inverter compressor drive board
is not connected properly
■Inverter compressor drive board is abnormal
■Mainboard is abnormal
Troubleshooting:
2.2.4.29
“C3” main control and inverter fan drive communication error
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will
display
Error judgment condition and method:
If ODU hasn
’t received inverter fan drive board data in continuous 30s, report the error.
Possible reason:
■Communication wire between ODU mainboard inside module and inverter fan drive board is not
connected properly
■Inverter fan drive board is abnormal
■Mainboard is abnormal