GREE GMV5 HR HEAT RECOVERY UNITS
59
R410A Refrigerant System
Allowable Value
m(feet)
Fitting Pipe
Total length (actual length) of fitting pipe
≤1000(3280-3/4)
L1+L2+L3+L4+…+L10+A11+A12+…+D2
1+D22
Length of farthest fitting
pipe m(feet)
Actual length
≤165(541-1/4)
L
Equivalent length
≤190(623-1/4)
——
Difference between the pipe length from the first
branch of IDU to the farthest IDU and the pipe
length from the first branch of IDU to the nearest
IDU
≤40(131-1/4)
L12-L11
Equivalent length from the first branch to the
furthest piping (1)
≤40(131-1/4)
L7+L8+L10+D22
Height difference
between outdoor unit
and indoor unit
Outdoor unit at upper(2)
≤90(295-1/4)
——
Outdoor unit at lower(2)
≤90(295-1/4)
——
Height difference between indoor units
≤30(98-2/4)
h1
Maximum length of Main pipe(3)
≤90(295-1/4)
L1
From IDU to its nearest branch (4)
≤40(131-1/4)
A11,A12,B21,B22,D21,D22
NOTICE!
(1) Normally, the pipe length from the first branch of IDU to the farthest IDU is 40m (131-1/4ft.).
Under the following conditions, the length can reach 90m (295-1/4ft.).
a)
Actual length of pipe in total: L1+L2x2+L3x2+L4x2+…+L10x2+A11+A12+…+D21+D22
≤1000m (3280-3/4ft.).
b) Length between each IDU and its nearest branch A11, A12, B21, B22, D21,
D22≤40m(131-1/4ft.).
c) Difference between the pipe length from the first branch of IDU to the farthest IDU and the
pipe length from the first branch of IDU to the nearest IDU: L12-
L11≤40m(131-1/4ft.).
(2)
When the maximum length of the main pipe from ODU to the first branch of IDU is≥90m
(295-1/4ft.), then adjust the pipe size of the gas pipe and liquid pipe of main pipe according to
the following table.
Outdoor Model
Size of connection between outdoor unit and the first indoor branch
Low pressure gas pipe mm(in.)
Liquid pipe mm(in.)
High pressure gas pipe mm(in.)
GMV-Q72WM/B-F(U)
No need to enlarge pipe size
No need to enlarge pipe size
No need to enlarge pipe size
GMV-Q96WM/B-F(U)
No need to enlarge pipe size
Ф12.7(1/2)
Φ22.2(7/8)
GMV-Q120WM/B-F(U)
No need to enlarge pipe size
Ф15.9(5/8)
Φ28.6(1-1/8)
GMV-Q144WM/B1-F(U)
Ф34.9(1-3/8)
Ф15.9(5/8)
Φ28.6(1-1/8)
GMV-Q144WM/B-F(U)
Ф34.9(1-3/8)
Ф15.9(5/8)
Φ28.6(1-1/8)
GMV-Q168WM/B1-F(U)
Ф34.9(1-3/8)
Ф19.05(3/4)
Φ28.6(1-1/8)
GMV-Q168WM/B-F(U)
Ф34.9(1-3/8)
Ф19.05(3/4)
Φ28.6(1-1/8)
GMV-Q192WM/B-F(U)
Ф34.9(1-3/8)
Ф19.05(3/4)
No need to enlarge pipe size
GMV-Q216WM/B-F(U)
Ф34.9(1-3/8)
Ф19.05(3/4)
No need to enlarge pipe size
GMV-Q240WM/B-F(U)
No need to enlarge pipe size
Ф19.05(3/4)
Ф34.9(1-3/8)
GMV-Q264WM/B-F(U)
No need to enlarge pipe size
Φ22.2(7/8)
Ф34.9(1-3/8)
GMV-Q288WM/B-F(U)
No need to enlarge pipe size
Φ22.2(7/8)
Ф34.9(1-3/8)
GMV-Q312WM/B-F(U)
No need to enlarge pipe size
Φ22.2(7/8)
Ф34.9(1-3/8)
Содержание GC201808-III
Страница 36: ...GREE GMV5 HR HEAT RECOVERY UNITS 32 Circuit diagram of GMV Q144WM B1 F U Circuit diagram of GMV Q168WM B1 F U ...
Страница 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Страница 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Страница 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Страница 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Страница 314: ...GREE GMV5 HR HEAT RECOVERY UNITS 310 4 Loosen the screws on the compressor drive as shown in the figure below ...
Страница 362: ...JF00302879 ...