GREE GMV5 HR HEAT RECOVERY UNITS
62
Basic module
Pipe between outdoor unit and the first indoor branch
Low pressure gas pipe
mm(inch)
Liquid pipe
mm(inch)
High pressure gas pipe
mm(inch)
GMV-Q72WM/B-F(U)
Φ19.05(3/4)
Φ9.52(3/8)
Φ15.9(5/8)
GMV-Q96WM/B-F(U)
Φ22.2(7/8)
Φ9.52(3/8)
Φ19.05(3/4)
GMV-Q120WM/B-F(U)
Φ28.6(1-1/8)
Φ12.7(1/2)
Φ22.2(7/8)
GMV-Q144WM/B1-F(U)
Φ28.6(1-1/8)
Φ12.7(1/2)
Φ22.2(7/8)
GMV-Q168WM/B1-F(U)
Φ28.6(1-1/8)
Φ15.9(5/8)
Φ22.2(7/8)
GMV-Q72WM/B-U(U)
Φ19.05(3/4)
Φ9.52(3/8)
Φ15.9(5/8)
GMV-Q96WM/B-U(U)
Φ22.2(7/8)
Φ9.52(3/8)
Φ19.05(3/4)
GMV-Q120WM/B-U(U)
Φ28.6(1-1/8)
Φ12.7(1/2)
Φ22.2(7/8)
(3) For multi-
module system, select appropriate branch (”M1/M2/M3”) connected to outdoor
module as per the pipe size of basic outdoor module. Pipe size of basic outdoor module is
shown as follows:
Pipe between module and outdoor branch “M1/M2/M3”
Basic module
Size of the pipe between module and outdoor branch
Low pressure gas pipe
mm(inch)
Liquid pipe
mm(inch)
High pressure gas pipe
mm(inch)
GMV-Q72WM/B-F(U)
Φ19.05(3/4)
Φ9.52(3/8)
Φ15.9(5/8)
GMV-Q96WM/B-F(U)
Φ22.2(7/8)
Φ9.52(3/8)
Φ19.05(3/4)
GMV-Q120WM/B-F(U)
Φ28.6(1-1/8)
Φ12.7(1/2)
Φ22.2(7/8)
GMV-Q144WM/B1-F(U)
Φ28.6(1-1/8)
Φ12.7(1/2)
Φ22.2(7/8)
GMV-Q168WM/B1-F(U)
Φ28.6(1-1/8)
Φ15.9(5/8)
Φ22.2(7/8)
GMV-Q72WM/B-U(U)
Φ19.05(3/4)
Φ9.52(3/8)
Φ15.9(5/8)
GMV-Q96WM/B-U(U)
Φ22.2(7/8)
Φ9.52(3/8)
Φ19.05(3/4)
GMV-Q120WM/B-U(U)
Φ28.6(1-1/8)
Φ12.7(1/2)
Φ22.2(7/8)
Selection of branch “Y1/Y2”of outdoor modules:
Module’s capacity C (Btu/h)
Model
Selection of branch of outdoor
modules
X
≤327500
ML01R
327500<X
ML02R
(4) Size of connection pipe
“M4” between branches of each basic module
Size of connection pipe between branches of each basic module is determined by the total rated
capacity of upstream modules.
Connection pipe
“M4” between branches of outdoor module
Total rated capacity of upstream
modules: Q
(
Btu/h
)
Size of connection pipe between branches of outdoor module
Low pressure gas pipe
mm(in.)
Liquid pipe
mm(in.)
High pressure gas pipe
mm(in.)
Q≤72000
Φ19.05(3/4)
Φ9.52(3/8)
Φ15.9(5/8)
72000<
Q≤96000
Φ22.2(7/8)
Φ9.52(3/8)
Φ19.05(3/4)
96000<
Q≤120000
Φ28.6(1-1/8)
Φ12.7(1/2)
Φ22.2(7/8)
120000<
Q≤144000
Φ28.6(1-1/8)
Φ12.7(1/2)
Φ22.2(7/8)
144000<
Q≤168000
Φ28.6(1-1/8)
Φ15.9(5/8)
Φ22.2(7/8)
168000<
Q≤216000
Φ28.6(1-1/8)
Φ15.9(5/8)
Φ28.6(1-1/8)
Содержание GC201808-III
Страница 36: ...GREE GMV5 HR HEAT RECOVERY UNITS 32 Circuit diagram of GMV Q144WM B1 F U Circuit diagram of GMV Q168WM B1 F U ...
Страница 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Страница 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Страница 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Страница 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Страница 314: ...GREE GMV5 HR HEAT RECOVERY UNITS 310 4 Loosen the screws on the compressor drive as shown in the figure below ...
Страница 362: ...JF00302879 ...