GREE GMV5 HR HEAT RECOVERY UNITS
176
Fault
code
Fault
Possible reasons
Solution
Primary reason
Secondary reason
Tertiary reason
Description
Confirmation
method
Description
Confirmation
method
Description
Confirmation
method
6.2.2 The fan
motor is not
properly
connected
with the
control board
of the motor
with the
communicati
on feedback
cable.
Manual
check
Reconnect it
properly.
6.2.3 The
control
board of the
fan's motor
is damaged.
Manual
check
Replace the
control board
of the motor.
6.2.4 The
main board
of the fan's
motor is
damaged.
Other
reasons
Replace the
motor.
6. Not
enough
refrigerant
Other
reasons
Incorrect
quantity of
refrigerant is
injected.
——
——
——
Check the
necessary
amount of
refrigerant
and inject
refrigerant
slowly via the
stop valve of
the
low-pressure
gas pipe.