GREE GMV5 HR HEAT RECOVERY UNITS
11
3 BASIC PARAMETERS OF UNIT
3.1 Basic Parameters of ODU
Outdoor Units_Heat Recovery
Ton
6
8
10
Model
-
GMV-Q72WM/B-F(U) GMV-Q96WM/B-F(U) GMV-Q120WM/B-F(U)
Module combination
-
GMV-Q72WM/B-F(U) GMV-Q96WM/B-F(U) GMV-Q120WM/B-F(U)
Performance
Nominal Cooling Capacity
①
Btu/h
72000
96000
120000
kW
21.1
28.1
35.2
Rated Cooling Capacity
Btu/h
67000
90000
111000
Nominal Heating Capacity
Btu/h
81000
108000
135000
kW
23.7
31.7
39.6
Rated Heating Capacity
Btu/h
75000
100000
126000
Cooling Power Input
kW
5.45
7.30
9.58
Heating Power Input
kW
5.80
7.85
10.42
Sound Pressure Level
dB(A)
61
62
63
Power Supply
-
208/230V 3~ 60Hz
Compressor
Type
-
Inverter scroll type
Inverter scroll type
Inverter scroll type
Number
N
1
1
2
Motor Output
②
kW
7.15
7.15
7.15+3.88
Starting Method
-
Inverter
Inverter
Inverter
Operating Range
-
13%~100%
11%~100%
12%~100%
Refrigeration Oil Brand
-
FVC68D or FV-68H
FVC68D or FV-68H
FVC68D or FV-68H
Oil Charge
③
Compressor
L
1.1
1.1
1.1+0.5
Oil separate tank
L
4.0
4.0
5.0
Total
L
5.1
5.1
6.6
Fan
Type×Quantity
-
Propeller×2
Propeller×2
Propeller×2
Motor output
W
750+750
750+750
750+750
Starting method
-
Inverter
Inverter
Inverter
Air flow rate
m
3
/h
14000
14000
14000
cfm
8240
8240
8240
Max. external static pressure
Pa
82
82
82
in.W.G
0.328
0.328
0.328
Ambient
temperature
range
Cooling
°C
-5~52
-5~52
-5~52
°F
23~125.6
23~125.6
23~125.6
Heating
°C
-20~24
-20~24
-20~24
°F
-4~75.2
-4~75.2
-4~75.2
Refrigerant
Refrigerant Type
-
R410A
R410A
R410A
Refrigerant Charge Volume
kg
9.6
11.2
11.7
lbs.
21.16
24.69
25.79
Control
-
EXV
EXV
EXV
Pipe
Connection
Low pressure Gas Pipe Size
mm
19.05
22.2
28.6
in.
3/4
7/8
1 1/8
high pressure gas pipe Size
mm
15.9
19.05
22.2
in.
5/8
3/4
7/8
Liquid Pipe Size
mm
9.52
9.52
12.7
in.
3/8
3/8
1/2
Содержание GC201808-III
Страница 36: ...GREE GMV5 HR HEAT RECOVERY UNITS 32 Circuit diagram of GMV Q144WM B1 F U Circuit diagram of GMV Q168WM B1 F U ...
Страница 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Страница 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Страница 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Страница 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Страница 314: ...GREE GMV5 HR HEAT RECOVERY UNITS 310 4 Loosen the screws on the compressor drive as shown in the figure below ...
Страница 362: ...JF00302879 ...