GREE GMV5 HR HEAT RECOVERY UNITS
30
4 ELECTRICAL PARAMETERS
4.1 Power Cable Wire Gauge and Circuit Breaker Selection of
outdoor unit
Outdoor units
Power Supply
Fuse Capacity
Minimum Circuit
Ampacity
Maximum Overcurrent
Protection
V/Ph/Hz
A
A
A
GMV-Q72WM/B-F(U)
208V/230V 3~ 60Hz
35
32
35
GMV-Q96WM/B-F(U)
208V/230V 3~ 60Hz
45
37
45
GMV-Q120WM/B-F(U)
208V/230V 3~ 60Hz
60
50
60
GMV-Q144WM/B1-F(U)
208V/230V 3~ 60Hz
70
55
70
GMV-Q168WM/B1-F(U)
208V/230V 3~ 60Hz
70
57
70
GMV-Q144WM/B-F(U)
208V/230V 3~ 60Hz
35+35
32+32
35+35
GMV-Q168WM/B-F(U)
208V/230V 3~ 60Hz
35+45
32+37
35+45
GMV-Q192WM/B-F(U)
208V/230V 3~ 60Hz
45+45
37+37
45+45
GMV-Q216WM/B-F(U)
208V/230V 3~ 60Hz
45+60
37+50
45+60
GMV-Q240WM/B-F(U)
208V/230V 3~ 60Hz
60+60
50+50
60+60
GMV-Q264WM/B-F(U)
208V/230V 3~ 60Hz
35+45+45
32+37+37
35+45+45
GMV-Q288WM/B-F(U)
208V/230V 3~ 60Hz
45+45+45
37+37+37
45+45+45
GMV-Q312WM/B-F(U)
208V/230V 3~ 60Hz
45+45+60
37+37+50
45+45+60
GMV-Q336WM/B-F(U)
208V/230V 3~ 60Hz
45+60+60
37+50+50
45+60+60
GMV-Q360WM/B-F(U)
208V/230V 3~ 60Hz
60+60+60
50+50+50
60+60+60
GMV-Q72WM/B-U(U)
460V 3~ 60Hz
20
15
20
GMV-Q96WM/B-U(U)
460V 3~ 60Hz
25
18
25
GMV-Q120WM/B-U(U)
460V 3~ 60Hz
30
25
30
GMV-Q144WM/B-U(U)
460V 3~ 60Hz
20+20
15+15
20+20
GMV-Q168WM/B-U(U)
460V 3~ 60Hz
20+25
15+18
20+25
GMV-Q192WM/B-U(U)
460V 3~ 60Hz
25+25
18+18
25+25
GMV-Q216WM/B-U(U)
460V 3~ 60Hz
25+30
18+25
25+30
GMV-Q240WM/B-U(U)
460V 3~ 60Hz
30+30
25+25
30+30
GMV-Q264WM/B-U(U)
460V 3~ 60Hz
20+25+25
15+18+18
20+25+25
GMV-Q288WM/B-U(U)
460V 3~ 60Hz
25+25+25
18+18+18
25+25+25
GMV-Q312WM/B-U(U)
460V 3~ 60Hz
25+25+30
18+18+25
25+25+30
GMV-Q336WM/B-U(U)
460V 3~ 60Hz
25+30+30
18+25+25
25+30+30
GMV-Q360WM/B-U(U)
460V 3~ 60Hz
30+30+30
25+25+25
30+30+30
Power cable wire gauge and circuit breaker must be selected based on the above parameters
and in compliance with local safety requirements. If there is conflict between above parameters
and national requirements, please contact the manufacture promptly.
If power cable wire gauge and circuit breaker is out of the above design range, fire hazard may
occur.
Содержание GC201808-III
Страница 36: ...GREE GMV5 HR HEAT RECOVERY UNITS 32 Circuit diagram of GMV Q144WM B1 F U Circuit diagram of GMV Q168WM B1 F U ...
Страница 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Страница 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Страница 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Страница 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Страница 314: ...GREE GMV5 HR HEAT RECOVERY UNITS 310 4 Loosen the screws on the compressor drive as shown in the figure below ...
Страница 362: ...JF00302879 ...