GREE GMV5 HR HEAT RECOVERY UNITS
217
■Detecting circuit is abnormal
Troubleshooting:
2.2.4.53
“db” Project debugging
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will
display
Error judgment condition and method:
This is a status code of project debugging, not a error code. When IDU or ODU displays this code, it
means the unit is under debugging status and the IDU cannot be operated.
Troubleshooting:
——
Possible reason:
——
2.2.4.54
“E1” High pressure protection
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will
display
Error judgment condition and method:
Judge through high pressure sensor detecting system real-time high pressure or action of high
pressure switch. If the sensor detects that high pressure is bigger than 65
°C
or high pressure switch is
cut off, it is judged that high pressure is too high and the system stops operation for protection.
Possible reason:
■Cut-off valve of ODU is not fully opened;
■High pressure sensor is abnormal;
■High pressure switch is abnormal;
■Outdoor or indoor fan is not working properly;
■IDU filter or air duct is blocked (heating mode);
■Ambient temperature is too high;
■Refrigerant charging amount is too much;
Содержание GC201808-III
Страница 36: ...GREE GMV5 HR HEAT RECOVERY UNITS 32 Circuit diagram of GMV Q144WM B1 F U Circuit diagram of GMV Q168WM B1 F U ...
Страница 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Страница 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Страница 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Страница 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Страница 314: ...GREE GMV5 HR HEAT RECOVERY UNITS 310 4 Loosen the screws on the compressor drive as shown in the figure below ...
Страница 362: ...JF00302879 ...