GREE GMV5 HR HEAT RECOVERY UNITS
63
Total rated capacity of upstream
modules: Q
(
Btu/h
)
Size of connection pipe between branches of outdoor module
Low pressure gas pipe
mm(in.)
Liquid pipe
mm(in.)
High pressure gas pipe
mm(in.)
216000<
Q≤240000
Φ34.9(1-3/8)
Φ15.9(5/8)
Φ28.6(1-1/8)
240000<
Q≤312000
Φ34.9(1-3/8)
Φ19.05(3/4)
Φ28.6(1-1/8)
312000<
Q≤336000
Φ34.9(1-3/8)
Φ19.05(3/4)
Φ28.6(1-1/8)
336000<
Q≤360000
Φ41.3(1-5/8)
Φ19.05(3/4)
Φ34.9(1-3/8)
(5) Size of connection pipe
“L” between the terminal outdoor branch and the first indoor branch.
Connection pipe “L”between outdoor unit and the first indoor branch
Basic module (single-module system)
Size of connection between outdoor unit and the first indoor branch
Low pressure gas pipe
mm(inch)
Liquid pipe
mm(inch)
High pressure gas pipe
mm(inch)
GMV-Q72WM/B-F(U)
Φ19.05(3/4)
Φ9.52(3/8)
Φ15.9(5/8)
GMV-Q96WM/B-F(U)
Φ22.2(7/8)
Φ9.52(3/8)
Φ19.05(3/4)
GMV-Q120WM/B-F(U)
Φ28.6(1-1/8)
Φ12.7(1/2)
Φ22.2(7/8)
GMV-Q144WM/B1-F(U)
Φ28.6(1-1/8)
Φ12.7(1/2)
Φ22.2(7/8)
GMV-Q168WM/B1-F(U)
Φ28.6(1-1/8)
Φ15.9(5/8)
Φ22.2(7/8)
GMV-Q144WM/B-F(U)
Φ28.6(1-1/8)
Φ12.7(1/2)
Φ22.2(7/8)
GMV-Q168WM/B-F(U)
Φ28.6(1-1/8)
Φ15.9(5/8)
Φ22.2(7/8)
GMV-Q192WM/B-F(U)
Φ28.6(1-1/8)
Φ15.9(5/8)
Φ28.6(1-1/8)
GMV-Q216WM/B-F(U)
Φ28.6(1-1/8)
Φ15.9(5/8)
Φ28.6(1-1/8)
GMV-Q240WM/B-F(U)
Ф34.9(1-3/8)
Φ15.9(5/8)
Φ28.6(1-1/8)
GMV-Q264WM/B-F(U)
Ф34.9(1-3/8)
Ф19.05(3/4)
Φ28.6(1-1/8)
GMV-Q288WM/B-F(U)
Ф34.9(1-3/8)
Ф19.05(3/4)
Φ28.6(1-1/8)
GMV-Q312WM/B-F(U)
Ф34.9(1-3/8)
Ф19.05(3/4)
Φ28.6(1-1/8)
GMV-Q336WM/B-F(U)
Ф34.9(1-3/8)
Ф19.05(3/4)
Φ28.6(1-1/8)
GMV-Q360WM/B-F(U)
Ф41.3(1-5/8)
Ф19.05(3/4)
Ф34.9(1-3/8)
GMV-Q72WM/B-U(U)
Φ19.05(3/4)
Φ9.52(3/8)
Φ15.9(5/8)
GMV-Q96WM/B-U(U)
Φ22.2(7/8)
Φ9.52(3/8)
Φ19.05(3/4)
GMV-Q120WM/B-U(U)
Φ28.6(1-1/8)
Φ12.7(1/2)
Φ22.2(7/8)
GMV-Q144WM/B-U(U)
Φ28.6(1-1/8)
Φ12.7(1/2)
Φ22.2(7/8)
GMV-Q168WM/B-U(U)
Φ28.6(1-1/8)
Φ15.9(5/8)
Φ22.2(7/8)
GMV-Q192WM/B-U(U)
Φ28.6(1-1/8)
Φ15.9(5/8)
Φ28.6(1-1/8)
GMV-Q216WM/B-U(U)
Φ28.6(1-1/8)
Φ15.9(5/8)
Φ28.6(1-1/8)
GMV-Q240WM/B-U(U)
Φ34.9(1-3/8)
Φ15.9(5/8)
Φ28.6(1-1/8)
GMV-Q264WM/B-U(U)
Φ34.9(1-3/8)
Ф19.05(3/4)
Φ28.6(1-1/8)
GMV-Q288WM/B-U(U)
Φ34.9(1-3/8)
Ф19.05(3/4)
Φ28.6(1-1/8)
GMV-Q312WM/B-U(U)
Φ34.9(1-3/8)
Ф19.05(3/4)
Φ28.6(1-1/8)
GMV-Q336WM/B-U(U)
Φ34.9(1-3/8)
Ф19.05(3/4)
Φ28.6(1-1/8)
GMV-Q360WM/B-U(U)
Φ41.3(1-5/8)
Ф19.05(3/4)
Φ34.9(1-3/8)
Содержание GC201808-III
Страница 36: ...GREE GMV5 HR HEAT RECOVERY UNITS 32 Circuit diagram of GMV Q144WM B1 F U Circuit diagram of GMV Q168WM B1 F U ...
Страница 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Страница 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Страница 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Страница 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Страница 314: ...GREE GMV5 HR HEAT RECOVERY UNITS 310 4 Loosen the screws on the compressor drive as shown in the figure below ...
Страница 362: ...JF00302879 ...