GREE GMV5 HR HEAT RECOVERY UNITS
137
Exception 2: If no master IDU is detected in step 02, the following faults are displayed in step 02:
LED1
LED2
LED3
Function Code
Display Mode
Current Progress
Display Mode
Current Status
Display Mode
db
On
02
On
L7
Blinking
In this case, all buttons are invalid. Users can set the master IDU through the commissioning
software, wired controller, or commissioning remote controller within one minute. If no master IDU is set
within one minute, the system will automatically set a master IDU. Then the system automatically enters
the next step.
Step 7: When the unit runs to step 03, users need to manually confirm the number of outdoor
modules. The main board of each module is displayed as follows:
Progress
Commissioning Code
Progress Code
Status Code
LED1
LED2
LED3
Code
Display Status
Code
Display Status
Code
Display Status
03_Module quantity confirmation
db
On
03
On
Module
quantity
Blinking
If the displayed quantity is consistent with the number of actually connected modules, press "SW7"
on the master unit to confirm. The main board is displayed as follows and the unit automatically enters
commissioning step 04.
Progress
Commissioning Code
Progress Code
Status Code
LED1
LED2
LED3
Code
Display Status
Code
Display Status
Code
Display Status
03_Module quantity confirmation
db
On
03
On
OC
On
If the displayed quantity is inconsistent with the number of actually connected modules, check
whether communication cables are correctly connected between modules in power-off status. Then
perform commissioning again.
It is very important to correctly confirm the number of ODUs. If the confirmed quantity is
inconsistent with the actual quantity, the system may improperly run.
Step 8: When the unit runs to step 04, users need to manually confirm the number of indoor
modules. The main board of each module is displayed as follows:
Progress
Commissioning Code
Progress Code
Status Code
LED1
LED2
LED3
Code
Display
Status
Code
Display
Status
Code
Display
Status
04_Indoor unit quantity
confirmation
db
On
04
On
Number of
connected IDUs
Blinking
Содержание GC201808-III
Страница 36: ...GREE GMV5 HR HEAT RECOVERY UNITS 32 Circuit diagram of GMV Q144WM B1 F U Circuit diagram of GMV Q168WM B1 F U ...
Страница 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Страница 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Страница 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Страница 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Страница 314: ...GREE GMV5 HR HEAT RECOVERY UNITS 310 4 Loosen the screws on the compressor drive as shown in the figure below ...
Страница 362: ...JF00302879 ...