background image

The OILPRESS pressure storage vessels
type 180.902 and type 240.902 are used to
transport heating oil to EL DIN 51603 to one
or more consumer points. 
The units consist of a casing with pressure
storage vessel, motor, pump and pressure
switch. During the transport process, the
heating oil is sucked in via the pump and
pressed into pressure storage vessel. The air
cushion in the storage vessel presses the oil
to the individual consumer points.
The motor is switched on by the pressure
switch at a lower working pressure of 1.6 bar,
and switched off again on reaching the upper
working pressure of 2.6 bar.

Pump Type 180.902

The planetary gear pump is driven by the
motor through a reduction gear. The pump is
characterised by its quiet running and low
wear. The pump is protected against conta-
mination by dirt by means of a circular filter
fitted to the pump body.

Pump Type 240.902

The feed pump is a planetary gear pump 
driven direct by the motor. The pump is 
characterised by its quiet running and low
wear. The pump is protected against conta-
mination by dirt by means of a circular filter
fitted to the pump body.

Casing

The casing is the supporting element of all
components. It houses the pump, motor,
pressure switch, pressure storage vessel, 
filter, over-pressure valve and drain valve.
Two taper union connections for the connec-
tion of 8-mm pipes and the plug screw with
non-return valve are fitted to the distributor
housing on the underside of the casing.

Pressure storage vessel

Disconnect the unit from the electrical power
supply before removing the cover hood (see

“Instructions”

). The lower part of the pres-

sure storage vessel is moulded into the
casing. A cylindrical diaphragm is clamped
between the lower and upper part, separa-
ting the air from the oil. An initial air pressure
of 1 bar is applied to the pressure storage
vessel through the valve located in the upper
part of the storage vessel. The air can there-
fore escape over the course of time by 

   

Single-line removal, no return flow.

   

For all interlinked battery tank systems without non-return valves in the suction line, 

     and for individual tanks without non-return valves in the suction line
     

(for further details, see under: No non-return valve may be installed in the suction line).

   

Tested to DIN EN 12514-1.

diffusion, increasing the switching frequency
of the pump. This change is corrected by
refilling the air cushion with the aid of an air
pump. When refilling with air, take care to
ensure that the test, over-pressure and drain
valve at the side of the unit are open. The ini-
tial air pressure in the pressure storage ves-
sel is correct when the manometer on the
pressure storage vessel shows 0 bar, and the
manometer on the pressure measurement
device (air pump) shows 1 bar.

Technical data                     Type 180.902

Motor:                                               230 V ~ 88 W
Delivery capacity:                             22 l/h at 0 bar pressure

Max. consumption:

                        

approx. 10 l/h

Permissible working pressure:           4.0 bar, limited by  

                                                           over-pressure valve

Upper supply limit:                           adjustable up to 25 m, 

                                                         factory set to 15 m

Suction head:                                   3 m
Pipe connection:                              Taper union 8x1 mm
Protection type:                                IP 34
Temperature of supply medium:      max. 40°C
Weight:                                             approx. 6 kg

Type 240.902

230 V ~ 50 W
46 l/h at 0 bar pressure

approx. 25 l/h

4.0 bar, limited by  
over-pressure valve
adjustable up to 25 m, 
factory set to 15 m
3 m
Taper union 8x1 mm
IP 34
max. 40°C
approx. 6 kg

Pressure Storage 
Vessel   

Type 180.902 · Type 240.902

Installation, maintenance and usage instructions

Pressure switch

Control lamp

Suction connection

Non-return valve 

(ventilation)

Filter

Air valve

Pressure storage vessel
initial pressure 1 bar

Pressure connection

Starter button

Test, over-pressure
and drain valve

245 mm

220 mm

Construction and functional
description

Wilhelm Keller 

GmbH & Co. KG 

Herdweg 1

72147 Nehren

DIN EN 12514-1

Содержание OILPRESS 180.902

Страница 1: ...al air pressure of 1 bar is applied to the pressure storage vessel through the valve located in the upper part of the storage vessel The air can there fore escape over the course of time by Single line removal no return flow For all interlinked battery tank systems without non return valves in the suction line and for individual tanks without non return valves in the suction line for further detai...

Страница 2: ...ring diagram type 180 902 Wiring diagram type 240 902 B C D E F A Fuse Control lamp Push button Motor Earth Condenser suppressor element Fuse Condenser Control lamp Push button Motor Earth Condenser suppressor element ...

Страница 3: ...X 020 232 Hood X X 099 422 Screw set for hood X X 100 422 Cover with screws X X 002 412 Pumpe X X 030 422 Spare parts for pump X 002 422 Pump complete X 017 232 Gear wheel X X 012 252 Lug screw X X 003 232 Manometer X X 110 422 Push button with connecting wires X 003 412 Motor complete X 063 202 Fan X 198 422 Motor complete X 445 422 Intermediate flange complete X 113 202 Terminal rail X 072 312 C...

Страница 4: ...t off valve can be ordered under article no 594 912 Supply line OILPRESS pressure storage units allow the use of a single line supply system see Piping diagram The line can be laid in any way required Oil pressure regulators must be installed so that the permissible pressure range of the oil regulator of 125 mm 3000 mm of oil is not exceeded at the combustion point The line from the oil pressure r...

Отзывы: