GREE GMV5 HR HEAT RECOVERY UNITS
284
LEDs are flashing. See the figure below:
Power
Run
D1
D2
D3
D4
D5
D6
D7
D8
Power
Running
IDU and ODU
communication
Main
system
M a i n -
system
Reserved
ODU
→
IDU
ODU
→
IDU
Inter-system
communication
System1
→
System2
System1
→
System2
If the LEDs flash, the ODU and IDUs normally communicate; if the LEDs are steadily on,
communication is faulty. Check communication lines connecting the ODU and IDUs.
NOTE:
After AP1 is replaced, you should power on the ODU and IDUs at the same time or power on
the ODU first; otherwise, “CC does not have module” will be prompted and a “C0 fault” alarm will be
reported by the IDUs.
(3) Master ODU engineering debug setting
Debug the entire system after master module AP1 replacement.
(4) System parameter setting
After system debug, reset system parameters. For details, refer to section 1 “ODU Function Setting”,
in part II, chapter III.
1.1.3 Cautions on Replacement of Slave ODU AP1
Before replacing slave module AP1, set DIP identical to that of the faulty AP1, check wiring, and
then power on the AP1.
After replacing the main board of master module, the complete unit must start commissioning
again.
If the main board of slave module is replaced, there is no need to start commissioning for the
complete unit.
1.2 Cautions on IDU AP1 Replacement
Before replacing IDU AP1, determine the module is a master IDU or a slave IDU.
1.2.1 AP1 DIP Setting and Jumper Cap Confirmation
Whatever the AP1 you replace is a master IDU AP1 or a slave IDU AP1, after it is replaced, check
original DIP setting and model.
Configure capacity DIP for the new AP1 and confirm its jumper cap, fan overload detect terminal,
and overflow detect terminal. They should be kept identical to those of the faulty AP1.
Their positions and corresponding silkscreen are as follows:
Capacity DIP: S1 (Capacity)
Jumper cap: U22 (Jump)
Overflow detect terminal: CN35(WATER-DTCT)
Fan overload detect terminal: CN36(OVC-FAN)
Содержание GC201808-III
Страница 36: ...GREE GMV5 HR HEAT RECOVERY UNITS 32 Circuit diagram of GMV Q144WM B1 F U Circuit diagram of GMV Q168WM B1 F U ...
Страница 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Страница 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Страница 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Страница 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Страница 314: ...GREE GMV5 HR HEAT RECOVERY UNITS 310 4 Loosen the screws on the compressor drive as shown in the figure below ...
Страница 362: ...JF00302879 ...