GREE GMV5 HR HEAT RECOVERY UNITS
110
Function
Code
Function
Name
Function Meaning
Factory Settings
Remark
Code
Meaning
limitation
settings
n5
Indoor unit
project
number offset
Prevents IDU project number conflicts when
different refrigerating systems are controlled in a
centralized manner.
——
——
It can only
be set.
n6
Fault query
Queries historical fault information of the ODU.
——
——
It can only be
queried.
n7
Parameter
query
Queries real-time operation parameters of the
ODU.
——
——
It can only be
queried.
n8
Indoor unit
project
number query
Displays project numberes of all IDUs through
ODU operations.
——
——
It can only be
queried.
n9
Online IDU
quantity query
Displays the number of online IDUs.
——
——
It can only be
queried.
nb
Outdoor unit
bar code
function query
Queries the entire-unit bar code and controller bar
code of ODU.
——
——
It can only be
queried.
If above function settings are incorrect, unit will run abnormal and compressor may even be
damaged.
3.2.2.2 Description of Functions
(1) A2 Refrigerant recovery operation
This function partially recovers refrigerants in a faulty module or IDU pipeline during unit
maintenance. The refrigerant recovery volume of each basic module is as follows:
Model of Basic Module
Maximum Refrigerant Recovery Volume
GMV-Q72WM/B-F(U)
9.6kg/21.16LBS
GMV-Q96WM/B-F(U)
11.2kg/24.69LBS
GMV-Q120WM/B-F(U)
11.7kg/25.79LBS
GMV-Q72WM/B-U(U)
9.6kg/21LBS
GMV-Q96WM/B-U(U)
11.2kg/25LBS
GMV-Q120WM/B-U(U)
11.7kg/25.79LBS
This function falls into two modes: faulty module refrigerant recovery and IDU pipeline
refrigerant recovery.
Refrigerant Recovery
Mode Code
Refrigerant Recovery
Mode Name
Remark
01
Indoor unit pipeline
refrigerant recovery
This mode is selected when an IDU fails and it is required to recover
refrigerants from the IDU pipeline to the out door units.
02
Basic module refrigerant
recovery
This mode is selected when a basic module fails and it is required to
recover refrigerants from this basic module to the other out door
units and pipeline.
When this function is enabled, the ODU automatically starts and recovers refrigerants to the
ODU or IDU pipeline.
Содержание GC201808-III
Страница 36: ...GREE GMV5 HR HEAT RECOVERY UNITS 32 Circuit diagram of GMV Q144WM B1 F U Circuit diagram of GMV Q168WM B1 F U ...
Страница 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Страница 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Страница 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Страница 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Страница 314: ...GREE GMV5 HR HEAT RECOVERY UNITS 310 4 Loosen the screws on the compressor drive as shown in the figure below ...
Страница 362: ...JF00302879 ...