GREE GMV5 HR HEAT RECOVERY UNITS
181
Fault
code
Fault
Possible reasons
Solution
Primary reason
Secondary reason
Tertiary reason
Description
Confirmation
method
Description
Confirmation
method
Description
Confirmation
method
5. Wrong
refrigerant
is injected.
Stop the whole
system. Test
the system's
balance
pressure 20
minutes later
and convert the
pressure into
the
corresponding
saturation
temperature.
Compare it with
the outdoor
ambient
temperature. If
the difference
is larger than
5°C, it is
exceptional.
——
——
——
——
Discharge
existing
refrigerant
and inject the
correct
refrigerant as
required.
6. Exhaust
temperature
sensor
failure
——
——
——
Replace the
temperature
sensor or
main board.
7. The
ambient
temperature
exceeds the
scope of
temperature
required for
safe
operation.
——
The outdoor
ambient
temperature
exceeds
50°C.
Measure the
ambient
temperature.
——
——
It is a normal
phenomenon
caused by the
protection
function.
E2
Low exhaust
temperature
protection
1. The
ODU's
electronic
expansion
valve is not
working
properly.
When the
system is
working in the
heating mode
and the ODU's
electronic
expansion
valve is opened
to 100PLS, the
intake
temperature of
the
corresponding
liquid-air
separator is
more than 1°C
lower than the
1.2 The
controlling
heating
electronic
expansion
of the main
board or the
electronic
expansion
valve of the
subcooler is
faulty.
Reset the
ODU. Listen
to the sound
and touch the
tube to see if
the electronic
expansion
valve is
reset. If it is
set, it is
normal.
Otherwise, it
is faulty.
1.2.1 The
control wire
of the
electronic
expansion
valve is not
connected to
the main
board.
Manual check
Connect the
electronic
expansion
valve's control
wire to the
main board.
1.2.2 The
control wire
that connects
the electronic
expansion
valve to the
main board is
broken.
Manual check
Repair or
replace the
control wire of
the electronic
expansion
valve.
Содержание GC201808-III
Страница 36: ...GREE GMV5 HR HEAT RECOVERY UNITS 32 Circuit diagram of GMV Q144WM B1 F U Circuit diagram of GMV Q168WM B1 F U ...
Страница 87: ...GREE GMV5 HR HEAT RECOVERY UNITS 83 1 External Connection for Individual Units ...
Страница 92: ...GREE GMV5 HR HEAT RECOVERY UNITS 88 ...
Страница 227: ...GREE GMV5 HR HEAT RECOVERY UNITS 223 Troubleshooting ...
Страница 286: ...GREE GMV5 HR HEAT RECOVERY UNITS 282 Troubleshooting ...
Страница 314: ...GREE GMV5 HR HEAT RECOVERY UNITS 310 4 Loosen the screws on the compressor drive as shown in the figure below ...
Страница 362: ...JF00302879 ...